GE B30 Instruction Manual page 147

Bus differential system, ur series
Hide thumbs Also See for B30:
Table of Contents

Advertisement

5 SETTINGS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The B30 supports the Distributed Network Protocol (DNP) version 3.0. The B30 can be used as a DNP slave device con-
nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the B30 maintains two sets of DNP
data change buffers and connection information, two DNP masters can actively communicate with the B30 at one time.
The IEC 60870-5-104 and DNP protocols cannot be simultaneously. When the IEC 60870-5-104 FUNCTION set-
ting is set to "Enabled", the DNP protocol will not be operational. When this setting is changed it will not become
NOTE
active until power to the relay has been cycled (off-to-on).
The DNP Channels sub-menu is shown below.
PATH: SETTINGS
PRODUCT SETUP
 DNP CHANNELS
MESSAGE
The
and
DNP CHANNEL 1 PORT
for each channel. Once DNP is assigned to a serial port, the Modbus protocol is disabled on that port. Note that COM1 can
be used only in non-Ethernet UR relays. When this setting is set to "Network - TCP", the DNP protocol can be used over
TCP/IP on channels 1 or 2. When this value is set to "Network - UDP", the DNP protocol can be used over UDP/IP on chan-
nel 1 only. Refer to Appendix E for additional information on the DNP protocol.
Changes to the
DNP CHANNEL 1 PORT
cycled to the relay.
NOTE
GE Multilin
DNP OTHER DEFAULT
DEADBAND: 30000
DNP TIME SYNC IIN
PERIOD: 1440 min
DNP MESSAGE FRAGMENT
SIZE: 240
DNP OBJECT 1
DEFAULT VARIATION: 2
DNP OBJECT 2
DEFAULT VARIATION: 2
DNP OBJECT 20
DEFAULT VARIATION: 1
DNP OBJECT 21
DEFAULT VARIATION: 1
DNP OBJECT 22
DEFAULT VARIATION: 1
DNP OBJECT 23
DEFAULT VARIATION: 2
DNP OBJECT 30
DEFAULT VARIATION: 1
DNP OBJECT 32
DEFAULT VARIATION: 1
DNP NUMBER OF PAIRED
CONTROL POINTS: 0
DNP TCP CONNECTION
TIMEOUT: 120 s


COMMUNICATIONS
DNP CHANNEL 1 PORT:
NONE
DNP CHANNEL 2 PORT:
NONE
settings select the communications port assigned to the DNP protocol
DNP CHANNEL 2 PORT
and
DNP CHANNEL 2 PORT
B30 Bus Differential System
Range: 0 to 100000000 in steps of 1
Range: 1 to 10080 min. in steps of 1
Range: 30 to 2048 in steps of 1
Range: 1, 2
Range: 1, 2
Range: 1, 2, 5, 6
Range: 1, 2, 9, 10
Range: 1, 2, 5, 6
Range: 1, 2, 5, 6
Range: 1, 2, 3, 4, 5
Range: 1, 2, 3, 4, 5, 7
Range: 0 to 32 in steps of 1
Range: 10 to 7200 s in steps of 1
DNP PROTOCOL
DNP CHANNELS
Range: NONE, COM1 - RS485, COM2 - RS485,
FRONT PANEL - RS232, NETWORK - TCP,
NETWORK - UDP
Range: NONE, COM1 - RS485, COM2 - RS485,
FRONT PANEL - RS232, NETWORK - TCP,
NETWORK - UDP
settings take effect only after power has been
5.2 PRODUCT SETUP
5
5-17