5.4 SYSTEM SETUP
a) SETTINGS

PATH: SETTINGS
SYSTEM SETUP
 FLEXCURVE A
FlexCurves™ A through D have settings for entering times to reset and operate at the following pickup levels: 0.00 to 0.98
and 1.03 to 20.00. This data is converted into two continuous curves by linear interpolation between data points. To enter a
custom FlexCurve™, enter the reset and operate times (using the VALUE keys) for each selected pickup point (using the
MESSAGE UP/DOWN keys) for the desired protection curve (A, B, C, or D).
Table 5–6: FLEXCURVE™ TABLE
RESET
TIME
RESET
MS
0.00
0.05
0.10
0.15
0.20
5
0.25
0.30
0.35
0.40
0.45
0.48
0.50
0.52
0.54
0.56
0.58
0.60
0.62
0.64
0.66
The relay using a given FlexCurve™ applies linear approximation for times between the user-entered points. Spe-
cial care must be applied when setting the two points that are close to the multiple of pickup of 1; that is, 0.98 pu
NOTE
and 1.03 pu. It is recommended to set the two times to a similar value; otherwise, the linear approximation may
result in undesired behavior for the operating quantity that is close to 1.00 pu.
5-76


FLEXCURVES

FLEXCURVE A TIME AT
0.00 xPKP:
TIME
OPERATE
MS
0.68
1.03
0.70
1.05
0.72
1.1
0.74
1.2
0.76
1.3
0.78
1.4
0.80
1.5
0.82
1.6
0.84
1.7
0.86
1.8
0.88
1.9
0.90
2.0
0.91
2.1
0.92
2.2
0.93
2.3
0.94
2.4
0.95
2.5
0.96
2.6
0.97
2.7
0.98
2.8
B30 Bus Differential System
FLEXCURVE A(D)
Range: 0 to 65535 ms in steps of 1
0 ms
TIME
OPERATE
TIME
OPERATE
MS
MS
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
4.0
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
5 SETTINGS
5.4.6 FLEXCURVES™
TIME
OPERATE
MS
4.9
10.5
5.0
11.0
5.1
11.5
5.2
12.0
5.3
12.5
5.4
13.0
5.5
13.5
5.6
14.0
5.7
14.5
5.8
15.0
5.9
15.5
6.0
16.0
6.5
16.5
7.0
17.0
7.5
17.5
8.0
18.0
8.5
18.5
9.0
19.0
9.5
19.5
10.0
20.0
GE Multilin
TIME
MS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents