Data; Refilling Refrigerant Charge; Compressor Technical Data - Mitsubishi Electric PUZ-ZM35VKA Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PUZ-ZM35VKA:
Table of Contents

Advertisement

5

DATA

5-1. REFILLING REFRIGERANT CHARGE (R32: kg)
Service Ref.
PUZ-ZM35VKA
PUZ-ZM50VKA
PUZ-ZM60VHA
PUZ-ZM71VHA

5-2. COMPRESSOR TECHNICAL DATA

Service Ref.
Compressor model
Winding
U-V
Resistance
U-W
(")
W-V
OCH653
10 m
20 m
30 m
2.0
2.0
2.0
2.8
2.8
2.8
PUZ-ZM35VKA
PUZ-ZM50VKA
SVB140FFSM
1.45
1.45
1.45
Piping length (one way)
40 m
50 m
2.15
2.3
3.2
3.6
Additional charge is required for pipes longer
than 30 m.
PUZ-ZM60VHA
PUZ-ZM71VHA
SVB172FFUM1
14
55 m
75 m
charged
3.6
(at 20:)
1.16
1.16
1.16
Initial
2.0
2.8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Puz-zm50vkaPuz-zm60vhaPuz-zm71vha