Removing The Reactor (Dcl) - Mitsubishi Electric PUZ-ZM35VKA Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PUZ-ZM35VKA:
Table of Contents

Advertisement

OPERATING PROCEDURE
10. Removing the high pressure switch (63H)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the electrical parts box. (See Photo 4)
(4) R emove 3 right side panel fixing screws (5 × 12) in the
rear of the unit and remove the right side panel.
(5) Pull out the lead wire of high pressure switch.
(6) Recover refrigerant.
(7) Remove the welded part of high pressure switch.
Note 1: Recover refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by
removing the right side panel.
Note 3: When installing the high pressure switch, cover it
with a wet cloth to prevent it from heating (100°C
or more), then braze the pipes so that the inside
of pipes are not oxidized.

11. Removing the reactor (DCL)

(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the electrical parts box. (See Photo 4)
(4) R emove 3 reactor fixing screws (4 × 16) and remove the
reactor.
Note 1: The reactor is attached to the rear of the electrical
parts box.
Note 2: The reactor has polarity: A care must be taken if
reassembling the reactor. (See Photo 10)
OCH653
PHOTOS
Photo 9
Lead wire of
high pressure switch
Photo 10
Reactor fixing screw
Reactor
(DCL)
Reactor fixing screws
*The marked wirings must be connected to the opposite
terminal of the reactor.
110
High pressure switch (63H)
Marked wirings*
Electrical parts box

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Puz-zm50vkaPuz-zm60vhaPuz-zm71vha

Table of Contents