ABB Fulscope 76J Series Model C Instructions Manual page 56

Table of Contents

Advertisement

Input Signal
Resistance Element
4 to 20 mA dc
0.25 to 1.25V dc
0 to 1V dc
0 to 5V dc
CHART DRIVE TYPE
Electric (General Purpose) 120V, 60Hz
Electric (General Purpose) 120V, 50Hz
Electric (General Purpose) 240V, 60Hz
Electric (General Purpose) 240V, 50Hz
Spring Wound, 9 Day wind
Spring Wound, 9 Day wind
Battery Operated
NOTES:
1. Do not use wire larger than 16 ga for voltage, current or
resistance element input connections. 24 ga or 0.5 mm wire is
recommended for mV and thermocouple input connections and
must be a twisted shielded pair or a twisted pair in conduit.
2. Run all signal wires in same conduit to minimize temperature
effects.
3. L
– Hot (live) wire
– Ground (earth) wire
N
– Common (neutral) wire
Cat. No.
Cust. No.
Also Refer to Dwgs.
Certified by
Printed in U.S.A.
©, 1998, ABB Instrumentation Inc.
1401L
1402L
1404L
1402L EME
Input Terminals
1404L EME
Input Terminals
Not for construction unless certified.
ABB No.
Date
Drawing applies only to the following Cat. Nos.:
Recorder: 76
J * T O O * * * * ** * C
Element: 1401
L
1402
1403
1404
* can be any digits
ABB Instrumentation
Connection Diagram
76J Recorders with
1401, 1402, 1403, 1404 EME Elements
WD-J-076-6
Rev 5
T T
A * ** ** * D
1401L EME
Input Terminals
Power Terminals
(View Below
Applies)
Sheet 1 of 1