845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 3-13: Major Errors
Table 3-8: Minor Self-test Errors
Self-test Error
Description of Problem How Often the Test is
1
Message
Order Code Error
Hardware doesn't
match order code
CPU S/N Invalid
CPU card doesn't have
valid data to match the
order code.
Slot"$" IO S/N
IO card located in slot $
2
Invalid
doesn't have valid data
to match the order
code.
Comms S/N Invalid Comms card doesn't
have valid data to
match the order code.
CPanel S/N Invalid Control Panel doesn't
have valid data to
match the order code.
PSU S/N Invalid
Power Supply Unit
doesn't have valid data
to match the order
code.
RTC Error
The CPU cannot read
the time from the real
time clock
Product Serial
The product serial
Invalid
number doesn't match
the product type
Comm Alert #1
Communication error
between CPU and
Comm Alert #2
Comms board
Comm Alert #3
FLASH Error
The permanent storage
memory has been
corrupted
SPI Error
Communication error
between CPU and LEDs,
Keypad or peripheral
memory devices
Invalid MAC
MAC address is not in
Address
the product range
Calibration Error
Unit has default
calibration values
FRONT CONTROL PANEL INTERFACE
What to do
Performed
Every 1 second
If alert doesn't self-reset then
contact factory. Otherwise
monitor re-occurrences as
Every 1 second
errors are detected and self-
reset
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Boot-up and Every 1
second