CHAPTER 4: SETPOINTS
NOTE:
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
If the 3-phase VT uses a delta connection and FREQUENCY INPUT is set to Ph VT Bnk1-J2,
the positive sequence voltage is used as the supervision voltage. In such condition, the true
supervision level is internally changed to 1/sqrt(3) of the user setting since the base of VT
here is the phase-phase voltage.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
For details see
Common
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
Setpoints.
PROTECTION
4–233