SERIAL PORT

Serial port
130
The following settings are available to configure the user-programmable self-tests.
Ethernet Port 1 Fail Function
Range: Enabled, Disabled
Default: Enabled
When this setting is "Disabled", the ETHERNET PORT 1 FAILURE alarm will not assert a
FlexLogic™ operand or write to the event recorder. Moreover, it will not trigger the ANY
MINOR ALARM or ANY SELF-TEST messages. When this setting is "Enabled", the
ETHERNET PORT 1 FAILURE alarm continues to function along with other major and
minor alarms. Refer to the Relay self-tests section in for additional information on major
and minor self-test alarms.
Ethernet Port 2 Fail Function
Range: Enabled, Disabled
Default: Disabled
When this setting is "Disabled", the ETHERNET PORT 2 FAILURE alarm will not assert a
FlexLogic™ operand or write to the event recorder. Moreover, it will not trigger the ANY
MINOR ALARM or ANY SELF-TEST messages. When this setting is "Enabled", the
ETHERNET PORT 2 FAILURE alarm continues to function along with other major and
minor alarms. Refer to the Relay self-tests section in for additional information on major
and minor self-test alarms.
Ethernet Port 3 Fail Function
Range: Enabled, Disabled
Default: Disabled
When this setting is "Disabled", the ETHERNET PORT 3 FAILURE alarm will not assert a
FlexLogic™ operand or write to the event recorder. Moreover, it will not trigger the ANY
MINOR ALARM or ANY SELF-TEST messages. When this setting is "Enabled", the
ETHERNET PORT 3 FAILURE alarm continues to function along with other major and
minor alarms. Refer to the Relay self-tests section in for additional information on major
and minor self-test alarms.
SNTP Fail Function
Range: Enabled, Disabled
Default: Enabled
When this setting is "Disabled", the SNTP FAILURE alarm will not assert a FlexLogic™
operand or write to the event recorder. Moreover, it will not trigger the ANY MINOR
ALARM or ANY SELF-TEST messages. When this setting is "Enabled", the SNTP FAILURE
alarm continues to function along with other major and minor alarms. Refer to the Relay
self-tests section in for additional information on major and minor self-test alarms.
IRIG-B Fail Function
Range: Enabled, Disabled
Default: Enabled
When this setting is "Disabled", the IRIG-B FAILURE alarm will not assert a FlexLogic™
operand or write to the event recorder. Moreover, it will not trigger the ANY MINOR
ALARM or ANY SELF-TEST messages. When this setting is "Enabled", the IRIG-B FAILURE
alarm continues to function along with other major and minor alarms. Refer to the Relay
self-tests section in for additional information on major and minor self-test alarms.
Plus
The D90
is equipped with one serial RS485 communication port. The RS485 port has
settings for baud rate and parity. It is important that these parameters agree with the
settings used on the computer or other equipment that is connected to these ports. This
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL