IEC 60870-5-104 COMMUNICATIONS

IEC 60870-5-104 communications

IEC 60870-5-104 protocol settings

98
Figure 73: DNP user point list configuration settings
The following settings are available for points 0 through 255.
DNP Binary Input Point 0
Range: any FlexLogic™ operand
Default: Off
This setting represents DNP binary input point 0 and is configured by assigning an
appropriate FlexLogic™ operand. Up to 256 binary input points can be configured for
the DNP protocol.
DNP Analog Input Point 0
Range: any FlexAnalog™ parameter
Default: Off
This setting represents DNP analog input point 0 and is configured by assigning an
appropriate FlexAnalog™ parameter. Up to 256 analog input points can be configured
for the DNP protocol.
The IEC 60870-5-104 server can support three clients simultaneously. It is capable of
reporting any indication or measurement and operating any output present in the device.
These point lists are shared with the DNP protocol.
Select the Settings > Communications > IEC 60870-5-104 > Protocol menu item to open
the IEC 60870-5-104 protocol configuration window.
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL