2.2 SPECIFICATIONS

2.2SPECIFICATIONSSPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
The operating times below include the activation time of a trip rated Form-A output contact unless otherwise indi-
cated. FlexLogic™ operands of a given element are 4 ms faster. This should be taken into account when using
FlexLogic™ to interconnect with other protection or control elements of the relay, building FlexLogic™ equations, or
NOTE
2
interfacing with other IEDs or power system devices via communications or different output contacts.
PHASE DISTANCE
Characteristic:
Number of zones:
Directionality:
Reach (secondary Ω):
Reach accuracy:
Distance:
Characteristic angle:
Comparator limit angle: 30 to 90° in steps of 1
Directional supervision:
Characteristic angle:
Limit angle:
PHASE DISTANCE OPERATING TIME CURVES
The operating times are response times of a microprocessor part of the relay. See output contacts specifications for estimation of the total
response time for a particular application. The operating times are average times including variables such as fault inception angle or type
of a voltage source (magnetic VTs and CVTs).
30
25
20
15
10
2-6
Mho (memory polarized or offset) or
Quad (memory polarized or non-direc-
tional), selectable individually per zone
5
forward, reverse, or non-directional per
zone
0.02 to 250.00 Ω in steps of 0.01
±5% including the effect of CVT tran-
sients up to an SIR of 30
30 to 90° in steps of 1
30 to 90° in steps of 1
30 to 90° in steps of 1
Phase Element (21P)
5
0
0%
10%
20%
30%
Fault Location [%]
D60 Line Distance Relay
Right blinder (Quad only):
Reach:
Characteristic angle:
Left Blinder (Quad only):
Reach:
Characteristic angle:
Time delay:
Timing accuracy:
Current supervision:
Level:
Pickup:
Dropout:
Memory duration:
VT location:
CT location:
Voltage supervision pickup (series compensation applications):
40%
50%
60%
70%
2 PRODUCT DESCRIPTION

2.2.1 PROTECTION ELEMENTS

0.02 to 500 Ω in steps of 0.01
60 to 90° in steps of 1
0.02 to 500 Ω in steps of 0.01
60 to 90° in steps of 1
0.000 to 65.535 s in steps of 0.001
±3% or 4 ms, whichever is greater
line-to-line current
0.050 to 30.000 pu in steps of 0.001
97 to 98%
5 to 25 cycles in steps of 1
all delta-wye and wye-delta transformers
all delta-wye and wye-delta transformers
0 to 5.000 pu in steps of 0.001
SIR = 0.1
SIR = 1
SIR = 10
SIR = 20
SIR = 30
80%
837717A1.CDR