Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Similarly for Signed comparison between inputs
Set the EnaAbs = Signed
Set the RefSource =Input REF
For absolute comparison between input and setting
Set the EnaAbs = Absolute
Set the RefSource = Set Value
SetValue shall be set between -2000000000 to 2000000000
Similarly for signed comparison between input and setting
Set the EnaAbs = Signed
Set the RefSource = Set Value
SetValue shall be set between -2000000000 to 2000000000

Comparator for real inputs - REALCOMP

Identification
Function description
Comparator for real inputs
Application
The function gives the possibility to monitor the level of real values in the system
relative to each other or to a fixed value. It is a basic arithmetic function that can be
used for monitoring, supervision, interlocking and other logics.
Setting guidelines
Setting procedure on the IED:
EnaAbs: This setting is used to select the comparison type between signed and
absolute values.
Absolute: Comparison is performed with absolute values of input and reference.
Signed: Comparison is performed with signed values of input and reference.
IEC 61850
IEC 60617
identification
identification
REALCOMP
Real<=>
Section 16
Logic
ANSI/IEEE C37.2
device number
619