9.2. Wiring and fitting capacities

(1) PUH-8, 10
Earth leakage breaker
*1, *2
capacity <A>
PUH-8
30 A 100 mA 0.1s or less
PUH-10
40 A 100 mA 0.1s or less
Notes:
*1: Connect an earth leakage breaker to the power supply.
*2: Use earth leakage breakers designed exclusively for ground fault protection only in combination with a local switch or a circuit breaker.
*3: The overcurrent protector using a Class-B fuse is shown.
*4: Power supply cords and indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 245 IEC 57)
*5: A switch with at least 3 mm contact separation in each pole shall be provided by the Air conditioner installation.
*6: The connection wiring between the outdoor and indoor units can be extended up to a maximum of 50 m.
*7: This device is intended for the connection to a power supply system with a maximum permissible system impedance ZMAX at the interface point (power
service box) of the user's supply.
The user has to ensure that this device is connected only to a power supply system which fulfills the requirement above.
If necessary, the user can ask the public power supply company for the system impedance at the interface point.
Warning:
Always use the designated cable for wiring, and connect it correctly. Secure
it so that the cable applies no external pressure to the terminal connection. If
the connection is faulty or the cable is not fully secured, overheating or fire
could result.
Caution:
Depending on the location of the unit, a current leakage breaker may be
required. If a current leakage breaker is not installed, electric shock could
result.
Do not use breakers or fuses with a capacity different from the correct
one. If large-capacity fuses, wire, or copper wiring are used, accident or
fire may result.
Table above is an example. The selection of other capacities should be deter-
mined in accordance with the relevant standards.
Types of cable/cord
Vinyl cab tire round cord: VCTF
Vinyl insulating vinyl sheath cable round type: VVR
Vinyl cab tire flat cord: VCTFK
Vinyl insulating vinyl sheath cable flat type: VVF
Vinyl insulating vinyl sheath cable for control: CVV
600 V vinyl cab tire cable: VCT
Vinyl insulating vinyl sheath cable for control: CVS
Warning:
Be sure to use specified cables and connect them firmly so that no external
wiring force is exerted on terminal connections. Loose connections may cause
heat or fire.

10. System control

10.1. Address settings

Outdoor unit address settings
When controlling a group, the address must be set for each outdoor unit.
During address setting, set all the dip switches SW1 (3 - 6) on the board to
<when shipped from factory: all OFF>. (Address setting is not necessary for
1:1 or Free multi-component systems.)
Settings using SW1 are given below.
Please set the mutually different address, and prevent the start up simultane-
ously. (In case of connecting with PEH-16, 20)
(SW1)
OFF
ON
Model
1
2
1
3
2 Error history clear
4
3 Refrigerant system
5
address setting
6
4
5
6
[Fig. 10.1.1] (P.7)
Local switch
Circuit
Switch
Overcurrent
breaker
protector *3 <A>
32
32
30
40
40
40
Operation by switch manipulation
OFF
ON
Ordinary
Clear
Outdoor unit address
Settings 0 - 15
Power cable *4
Earth cable
2
2
4.0 mm
or more
4.0 mm
or more
2
2
6.0 mm
or more
6.0 mm
or more
Caution:
Some installation sites may required installation of an earth leakage
breaker. Failure to install it may result in an electric shock.
Always use an earth leakage breaker and fuse with the specified capac-
ity. Use of a fuse with a capacity larger than that specified, or use of a
piece of wire or copper wire may cause breakdown or fire.
Example
[Fig. 9.2.1] (P.6)
(1) Connecting with PEH-8, 10
(2) Grouping (16 outdoor units) [Example: PEH-8, 10]
(3) Connecting with PEH-16, 20
(4) Grouping (16 outdoor units) [Connecting with PEH-16, 20]
A Power supply
C Circuit breaker or local switch
E Indoor unit

9.3. Location of wiring connections

Using the conduit mounting plates
Conduit mounting plates are supplied in three sizes (ø27, ø34, ø40). Choose
the size of mounting plate that matches the outer diameter of the conduit being
used.
Tie up wirings with cable strap mounted at the panel and lead it to control box.
[Fig. 9.3.1] (P.6)
A Conduit mounting plate (supplied)
C Indoor unit connection hole
10.2. Examples of refrigerant system address
setting
Ex.
Indoor unit
1
PEH-8, 10
2
PEH-16, 20
* Set the refrigerant system address of one outdoor unit to 00 for the power supply
to the remote controller.
(The refrigerant system address is set to 00 when shipped from the factory.)
Do not duplicate the refrigerant system address settings within the same system.
10.3. Capacity control setting method (PEH-
16, 20 only)
With the PEH-16, 20 which has two outdoor units, the capacity can be controlled to
0%, 50% or 100%.
This is set by setting the outdoor unit side dip switches as shown in the table below
before turning the power on.
No.1 side outdoor unit
DipSW5-1
OFF
Defrost signal cable
Indoor and outdoor
(Connecting with
connection wiring *4
PEH-16, 20)
2
2
1.5 mm
or more
0.75mm
or more
2
2
1.5 mm
or more
0.75mm
or more
B Earth leakage breaker
D Remote controller
F Outdoor unit (Address)
B Power supply wiring hole
D Tie up wirings with cable strap
Outdoor unit refrigerant
Outdoor unit
system address
00
No.1
00
No.2
01~15
No.2 side outdoor unit
ON
Max. Permissible
System impedance,
ZMAX *7
0.08
0.05
Remote controller
power supply unit
13