CHAPTER 6: SETPOINTS
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
TRIGGER ON PKP
Range: Off, On
Default: Off
Selection of "Yes" setting enables triggering for the recorder upon Pickup condition
detected from any protection or control element.
TRIGGER ON DPO
Range: Off, On
Default: Off
Selection of "Yes" setting enables triggering for the recorder upon a Dropout condition
detected from any protection or control element.
TRIGGER ON TRIP
Range: Off, On
Default: Off
Selection of "Yes" setting enables triggering for the recorder upon Trip condition
detected from any protection or control element.
TRIGGER ON ALARM
Range: Off, On
Default: Off
Selection of "Yes" setting enables triggering for the recorder upon Alarm condition
detected from any protection or control element.
TRIGGER ON INPUT 1 to 3
Range: Off, Contact Input 1 to 10, Virtual Input 1 to 32, Remote Input 1 to 32, Logic
Element 1 to 16, CT Fail Alarm PKP, CT Fail Alarm OP
Default: Off
Selection of input or logic element from the settings range enables triggering input for
the recorder. A record will be triggered if the status of the selected input changes to "On".
TRIGGER ON INPUT 1 to 3
Range: Off, Contact Input 1 to 10, Virtual Input 1 to 32, Remote Input 1 to 32, Logic
Element 1 to 16
Default: Off
Selection of input or logic element from the settings range enables triggering input for
the recorder. A record will be triggered if the status of the selected input changes to "On".
S1 RELAY SETUP
6–17