5.6 GROUPED ELEMENTS
a) MAIN MENU
PATH: SETTINGS
GROUPED ELEMENTS
 VOLTAGE ELEMENTS
5
These protection elements can be used for a variety of applications such as:
Undervoltage Protection: For voltage sensitive loads, such as induction motors, a drop in voltage increases the
drawn current which may cause dangerous overheating in the motor. The undervoltage protection feature can be used
to either cause a trip or generate an alarm when the voltage drops below a specified voltage setting for a specified time
delay.
Permissive Functions: The undervoltage feature may be used to block the functioning of external devices by operat-
ing an output relay when the voltage falls below the specified voltage setting. The undervoltage feature may also be
used to block the functioning of other elements through the block feature of those elements.
Source Transfer Schemes: In the event of an undervoltage, a transfer signal may be generated to transfer a load
from its normal source to a standby or emergency power source.
5-222
SETTING GROUP 1(6)
 PHASE
 UNDERVOLTAGE1
 PHASE
MESSAGE
 UNDERVOLTAGE2
 PHASE
MESSAGE
 OVERVOLTAGE1
 NEUTRAL OV1
MESSAGE
 NEUTRAL OV2
MESSAGE
 NEUTRAL OV3
MESSAGE
 NEG SEQ OV1
MESSAGE
 NEG SEQ OV2
MESSAGE
 NEG SEQ OV3
MESSAGE
 AUXILIARY UV1
MESSAGE
 AUXILIARY UV2
MESSAGE
 AUXILIARY OV1
MESSAGE
 AUXILIARY OV2
MESSAGE
 VOLTS/HZ 1
MESSAGE
 VOLTS/HZ 2
MESSAGE
G60 Generator Protection System


VOLTAGE ELEMENTS

See page 5–224.
See page 5–224.
See page 5–225.
See page 5–226.
See page 5–226.
See page 5–226.
See page 5–227.
See page 5–227.
See page 5–227.
See page 5–228.
See page 5–228.
See page 5–229.
See page 5–229.
See page 5–230.
See page 5–230.
5 SETTINGS
5.6.13 VOLTAGE ELEMENTS
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents