5.8 INPUTS/OUTPUTS
GOOSE Analogs that represent current, voltage, power, frequency, angles, or power factor can be used in a FlexEle-
ment. The following text must be used in the UNITS setting, to represent these types of analogs: A, V, W, var, VA, Hz,
deg, and no text (blank setting) for power factor.
GOOSE Analogs can be compared to other GOOSE Analogs with any character string or no string.
GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna-
log values in other G60 features, such as FlexElements. The base factor is applied to the GOOSE analog input Flex-
Analog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
The per-unit base setting represents thousands, not single units. For example, a PU base of 1.000 is actually 1000 and
a PU base of 0.001 is 1.
When using GOOSE Analogs and PU base in FlexElements, the largest value that can be displayed in the FlexEle-
ment actual values is 2,140,000.000.
Table 5–35: GOOSE ANALOG INPUT BASE UNITS
ELEMENT
DCmA
FREQUENCY
FREQUENCY RATE OF CHANGE
PHASE ANGLE
POWER FACTOR
RTDs
5
SENSITIVE DIR POWER
(Sns Dir Power)
SOURCE CURRENT
SOURCE ENERGY
(Positive and Negative Watthours,
Positive and Negative Varhours)
SOURCE POWER
SOURCE VOLTAGE
STATOR DIFFERENTIAL
CURRENT
(Stator Diff Iar, Ibr, and Icr)
STATOR GROUND 3RD
HARMONIC VOLTAGES
(Stator Gnd Vn/V0 3rd)
STATOR RESTRAINING
CURRENT
(Stator Diff Iad, Ibd, and Icd)
SYNCHROCHECK
(Max Delta Volts)
VOLTS PER HERTZ
The GOOSE analog input FlexAnalog values are available for use in other G60 functions that use FlexAnalog values.

PATH: SETTINGS
INPUTS/OUTPUTS
 GOOSE UINTEGER
 INPUT 1
The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger values between any two UR-series
devices. The following settings are available for each GOOSE uinteger input.
5-308
BASE UNITS
BASE = maximum value of the
under the +IN and –IN inputs.
f
= 1 Hz
BASE
df/dt
= 1 Hz/s
BASE
ϕ
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
= maximum value of 3 × V
P
BASE
configured for the sensitive power directional element(s).
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
E
= 10000 MWh or MVAh, respectively
BASE
P
= maximum value of V
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
I
= maximum primary RMS value of the +IN and –IN inputs
BASE
(CT primary for source currents, and bus reference primary current for bus differential currents)
V
= Primary auxiliary voltage of the
BASE
I
= maximum primary RMS value of the +IN and –IN inputs
BASE
(CT primary for source currents, and bus reference primary current for bus differential currents)
V
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
BASE
BASE = 1.00 pu

IEC 61850 GOOSE UINTEGERS
UINTEGER
1000
UINTEGER
MESSAGE
MODE: Default Value
G60 Generator Protection System
setting for the two transducers configured
DCMA INPUT MAX
× I
for the +IN and –IN inputs of the sources
BASE
BASE
× I
for the +IN and –IN inputs
BASE
BASE
STATOR GROUND SOURCE

5.8.13 IEC 61850 GOOSE INTEGERS


GOOSE UINTEGER INPUT 1(16)
Range: 0 to 429496295 in steps of 1
1 DEFAULT:
Range: Default Value, Last Known
1 DEFAULT
5 SETTINGS