Vega VEGASON 61 Quick Setup Manual

Vega VEGASON 61 Quick Setup Manual

Ultrasonic sensor for continuous level measurement
Hide thumbs Also See for VEGASON 61:

Advertisement

Quick setup guide
Ultrasonic sensor for continuous level
measurement
VEGASON 61
4 ... 20 mA/HART - four-wire
Document ID: 51856

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VEGASON 61 and is the answer not in the manual?

Questions and answers

Summary of Contents for Vega VEGASON 61

  • Page 1 Quick setup guide Ultrasonic sensor for continuous level measurement VEGASON 61 4 … 20 mA/HART - four-wire Document ID: 51856...
  • Page 2: Table Of Contents

    "www.vega.com". Operating instructions VEGASON 61 - 4 … 20 mA/HART - four- wire: Document-ID 28778 Editing status of the quick setup guide: 2016-06-28 VEGASON 61 • 4 … 20 mA/HART - four-wire...
  • Page 3: For Your Safety

    During work on and with the device the required personal protective equipment must always be worn. Appropriate use VEGASON 61 is a sensor for continuous level measurement. You can find detailed information about the area of application in chapter "Product description". Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions.
  • Page 4: Safety Label On The Instrument

    That is why we have introduced an environment management system with the goal of continuously improving company environmental pro- tection. The environment management system is certified according to DIN EN ISO 14001. Please help us fulfil this obligation by observing the environmental instructions in this manual: • Chapter "Packaging, transport and storage" • Chapter "Disposal" VEGASON 61 • 4 … 20 mA/HART - four-wire...
  • Page 5: Product Description

    "VEGA Tools" and "Instrument search". You can find the serial number on the inside of the instrument as well as on the type label on the outside. Alternatively, you can access the data via your smartphone: • Download the smartphone app "VEGA Tools" from the "Apple App Store" or the "Google Play Store" • Scan the Data Matrix code on the type label of the instrument or •...
  • Page 6: Mounting

    Fig. 1: Minimum distance to the max. level Dead zone Reference plane Mounting Mount the sensor at least 200 mm (7.874 in) away from the vessel wall. > 200 mm Fig. 2: Mounting on round vessel tops Reference plane Vessel center or symmetry axis VEGASON 61 • 4 … 20 mA/HART - four-wire...
  • Page 7: Connecting To Power Supply

    12. Screw the housing lid back on The electrical connection is finished. Fig. 3: Connection steps 5 and 6 VEGASON 61 • 4 … 20 mA/HART - four-wire...
  • Page 8: Wiring Plan, Double Chamber Housing

    4 Connecting to power supply Wiring plan, double chamber housing Wiring plan 4...20mA L1 N 4 ... 20 mA Fig. 4: Wiring plan, double chamber housing Voltage supply Signal output VEGASON 61 • 4 … 20 mA/HART - four-wire...
  • Page 9: Set Up With The Display And Adjustment Module Plicscom

    The display and adjustment module is powered by the sensor, an ad- ditional connection is not necessary. Fig. 5: Insert display and adjustment module Note: If you intend to retrofit the instrument with a display and adjustment module for continuous measured value indication, a higher lid with an inspection glass is required. VEGASON 61 • 4 … 20 mA/HART - four-wire...
  • Page 10: Setup Steps

    The actual level is then calculated on the basis of these entered values. At the same time, the operating range of the sensor is limited from maximum range to the requested range. VEGASON 61 • 4 … 20 mA/HART - four-wire...
  • Page 11 3. Confirm "False signal suppression - Change now" with [OK] and select in the below menu "Create new". Enter the actual distance from the sensor to the product surface. All false signals in this area are detected by the sensor and saved after confirming with [OK]. VEGASON 61 • 4 … 20 mA/HART - four-wire...
  • Page 12: Menu Schematic

    Linear Sensor Display Basic adjustment ▶ Display Diagnostics Service Info Displayed value Display unit Scaling Backlight ▼ Scaled Volume 0 % = 0.0 m³ Switched off m³ 100 % = 100.0 m³ VEGASON 61 • 4 … 20 mA/HART - four-wire...
  • Page 13 Basic adjustment Display Diagnostics Service ▶ Info Instrument type Date of manufacture Last change using PC Sensor characteristics 7. June 2016 Software version Display now? Serial number 3.80 10. June 2016 12345678 VEGASON 61 • 4 … 20 mA/HART - four-wire...
  • Page 14: Supplement

    Ʋ Double chamber housing – 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 x blind plug M20 x 1.5; plug M12 x 1 for VEGADIS 61 (optional) – 1 x closing cap ½ NPT, 1 x blind plug ½ NPT, plug M12 x 1 for VEGADIS 61 (optional) – 1 x plug (depending on the version), 1 x blind plug M20 x 1.5; plug M12 x 1 for VEGADIS 61 (optional) Spring-loaded terminals for wire cross- < 2.5 mm² (AWG 14) section Voltage supply Operating voltage Ʋ Non-Ex and Ex-d instrument 20 … 72 V DC, 20 … 253 V AC, 50/60 Hz Power consumption max. 4 VA; 2.1 W VEGASON 61 • 4 … 20 mA/HART - four-wire...
  • Page 15 Notes VEGASON 61 • 4 … 20 mA/HART - four-wire...
  • Page 16: Information

    Subject to change without prior notice © VEGA Grieshaber KG, Schiltach/Germany 2016 VEGA Grieshaber KG Phone +49 7836 50-0 Am Hohenstein 113...