    Operating Instructions VEGASON 61 4 … 20 mA/HART four-wire Ultrasonic...
  • Page 2: Table Of Contents

    Parameter adjustment with AMS™ and PDM ..38 Saving the parameter adjustment data ... . 38 VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 3 Instructions manuals for accessories and replacement parts Tip: To ensure reliable setup and operation of your VEGASON 61, we offer accessories and replacement parts. The associated documents are: 27835 - Indicating and adjustment module PLICSCOM 32628 - Interface adapter VEGACONNECT...
  • Page 4: About This Document

    List The dot set in front indicates a list with no implied sequence. à Action This arrow indicates a single action. Sequence Numbers set in front indicate successive steps in a procedure. VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 5: For Your Safety

    During work on and with the device the required personal protective equipment must always be worn. 2.2 Appropriate use VEGASON 61 is a sensor for continuous level measurement. You can find detailed information on the application range in chapter "Product description".
  • Page 6: Safety Approval Markings And Safety Tips

    The range of available functions depends on the respective software version of the individual components. The software version of VEGASON 61 can be determined as follows: via PACTware on the type label of the electronics via the indicating and adjustment module You can view all software histories on our website www.vega.com.
  • Page 7 2 For your safety Chapter "Packaging, transport and storage" Chapter "Disposal" VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 8: Product Description

    Housing cover, optionally available with indicating and adjustment module PLICSCOM The components are available in different versions. Fig. 1: VEGASON 61 - Aluminium double chamber housing Housing cover with integrated PLICSCOM (optional) Housing with electronics, optionally available with plug connector Process fitting with transducer...
  • Page 9: Principle Of Operation

    In addition to the type label outside, you can also find the serial number on the inside of the instrument. 3.2 Principle of operation VEGASON 61 is an ultrasonic sensor for continuous level measure- Application area ment. It is suitable for liquids and solids in virtually all industries, particularly in the water and waste water industry.
  • Page 10: Packaging, Transport And Storage

    Protected against solar radiation Avoiding mechanical shock and vibration Storage and transport temperature see chapter "Supplement - Storage and transport temperature Technical data - Ambient conditions" Relative humidity 20 … 85 % VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 11: Mounting

    Make sure that a min. distance - the so called dead zone - below the reference plane is maintained in which a measurement is not possible. The exact value of the dead zone is stated in chapter "Technical data". VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 12 (max. measuring distance) Measuring range Gauge pressure in the vessel does not influence VEGASON 61. Low Pressure/Vacuum pressure or vacuum does, however, damp the ultrasonic pulses. This influences the measuring result, particularly if the level is very low.
  • Page 13: Mounting Instructions

    4 Mounting 4.2 Mounting instructions Screw VEGASON 61 into the mounting socket with an appropriate Screwing in spanner applied to the hexagon of the process fitting. Max. torque see chapter "Technical data". Warning: The housing must not be used to screw the instrument in! Applying tightening force can damage internal parts of the housing.
  • Page 14 Fig. 7: Recommended socket mounting If the reflective properties of the medium are good, you can mount VEGASON 61 on sockets higher than the transducer length. You will find recommended values for socket heights in the following illustration. The socket end should be smooth and burr-free, if possible also rounded.
  • Page 15 Fig. 9: Alignment in liquids To reduce the min. distance to the medium, you can also mount VEGASON 61 with a beam deflector. By doing this, it is possible to fill the vessel nearly to maximum. Such an arrangement is suitable primarily for open vessels such as e.g.
  • Page 16 If there are agitators in the vessel, a false echo storage should be Agitators carried out with the agitators in motion. This ensures that the interfering reflections from the agitators are saved with the blades in different positions. Fig. 12: Agitators VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 17 Air turbulences outdoor installations or air turbulence, e.g. by cyclone extraction you should mount VEGASON 61 in a standpipe or use a different measuring principle, e.g. radar or guided radar (TDR). By using a standpipe (surge or bypass tube), the influence of vessel Standpipe measurement installations, foam generation and turbulence is excluded.
  • Page 18 Fig. 14: Standpipe in tank Vent hole: ø 5 … 10 mm (0.197 … 0.394 in) VEGASON 61 can be used from tube diameters of 40 mm (1.575 in). Avoid large gaps and thick welding joints when connecting the tubes.
  • Page 19: Connecting To Power Supply

    (0.2 … 0.35 in) ensures the seal effect of the cable gland. If you are using cable with a different diameter or cross-section, exchange the seal or use a suitable cable gland. VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 20: Connection Procedure

    11 Connect the lead cable for power supply in the same way according to the wiring plan, in addition connect the ground conductor to the inner ground terminal. VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 21: Wiring Plan, Double Chamber Housing

    Fig. 16: Double chamber housing Housing cover, connection compartment Blind stopper or plug M12 x 1 for VEGADIS 61 (optional) Housing cover, electronics compartment Filter element for air pressure compensation Cable gland VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 22 4... 20mA L1 N Fig. 18: Connection compartment, double chamber housing Spring-loaded terminals for signal output Ground terminal for connection of the ground conductor and screen Spring-loaded terminals for voltage supply VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 23: Switch On Phase

    Fig. 19: Wiring plan, double chamber housing Power supply Signal output 5.4 Switch on phase After connecting VEGASON 61 to power supply or after a voltage Switch on phase recurrence, the instrument carries out a self-check for approx. 30 seconds: Internal check of the electronics Indication of the instrument type, the firmware as well as the...
  • Page 24: Set Up With The Indicating And Adjustment Module Plicscom

    Screw housing cover with inspection window tightly back on Removal is carried out in reverse order. The indicating and adjustment module is powered by the sensor, an additional connection is not necessary. VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 25 Fig. 20: Mounting the indicating and adjustment module Note: If you intend to retrofit the instrument with an indicating and adjustment module for continuous measured value indication, a higher cover with an inspection glass is required. VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 26: Adjustment System

    The functions of the individual keys are shown in the above illustration. Approx. 10 minutes after the last pressing of a key, an automatic reset to measured value indication is triggered. Any values not confirmed with [OK] will not be saved. VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 27: Setup Procedure

    HART mode Standard Address 0 As VEGASON 61 is a distance measuring instrument, the distance Parameter adjustment from the sensor to the product surface is measured. To have the real product level displayed, an allocation of the measured distance to the percentage height must be made.
  • Page 28 With solids, you can also choose between "Powder/Dust", "Granular/ Pellets" or "Ballast/Pebbels". Through this additional selection, the sensor is adapted perfectly to the product and measurement reliability, particularly in products with bad reflective properties, is considerably increased. VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 29 "Display". Linearisation curve linear Enter the requested parameter via the appropriate keys, save your settings and jump to the next menu item with the [->] key. VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 30 The filling level would then no longer be detectable in this area. The menu item "Extended setting" offers the possibility to optimise Extended setting/Quick VEGASON 61 for applications in which the level changes very quickly. level change For this reason, select the function "Quick level change > 1 m/min.".
  • Page 31 Function Reset value Max. adjustment 0 m(d) Min. adjustment Meas. range end in m(d) Medium Liquid Vessel form not known Sensor-specific basic adjustment. Depending on the sensor type, see chapter "Technical data". VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 32 You will find a detailed description of these menu items in the operating instructions manual "Indicating and adjustment module". Special parameters are parameters which are set customer-specifically on the service level with the adjustment software PACTware. VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 33: Menu Plan Ultrasonic Sensor

    Service Info Displayed value Display unit Scaling Lighting 0 % = 0.0 m³ ▼ Scaled Volume Switched off 100 % = 100.0 m³ m³ Diagnostics Basic adjustment Display ▶ Diagnostics Service Info VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 34 Basic adjustment Display Diagnostics Service ▶ Info Sensor type Date of manufacture Last change using PC Sensor characteristics 10. January 2008 Software version Display now? Serial number 3.50 10. January 2008 12345678 VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 35: Saving The Parameter Adjustment Data

    They are hence available for multiple use or service purposes. If VEGASON 61 is equipped with an indicating and adjustment module, the most important data can be read out of the sensor into indicating and adjustment module. The procedure is described in the operating instructions manual "Indicating and adjustment module"...
  • Page 36: Setup With Pactware And Other Adjustment Programs

    Sensor External connection via I²C interface TWIST Fig. 23: Connection via I²C connection cable I²C bus (com.) interface on the sensor I²C connection cable of VEGACONNECT VEGACONNECT USB cable to the PC VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 37: Parameter Adjustment With Pactware

    With power supply units with integrated HART resistance (internal resistance approx. 250 Ω), an additional external resistance is not necessary. This applies, e. g. to the VEGA instruments VEGATRENN 149A, VEGADIS 371, VEGAMET 381). Common Ex separators are also usually equipped with a sufficient current limitation resistance. In such cases, VEGACONNECT 4 can be connected parallel to the 4 …...
  • Page 38: Parameter Adjustment With Ams™ And Pdm

    7 Setup with PACTware and other adjustment programs Note: Keep in mind that for setup of VEGASON 61, DTM-Collection in the actual version must be used. All currently available VEGA DTMs are provided in the DTM Collection on CD and can be obtained from the responsible VEGA agency for a token fee.
  • Page 39: Maintenance And Fault Rectification

    DTM. In many cases, the causes can be determined in this way and faults can be rectified. However, should these measures not be successful, call the VEGA 24 hour service hotline service hotline in urgent cases under the phone no. +49 1805 858550.
  • Page 40: Exchanging The Electronics Module

    Or on site by the user In both cases, the sensor serial number is needed. The serial numbers are stated on the type label of the instrument, inside the housing or on the delivery note. VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 41: Software Update

    Prepare update to the instrument via VEGACONNECT. Start PACTware and provide connection to the sensor, e.g. via the VEGA project assistant. Close the parameter window of the sensor, as far as open. Go in the PACTware menu bar to "Instrument data", "Additional Load software into sen- functions"...
  • Page 42 8 Maintenance and fault rectification Please ask the agency serving you for the address of your return shipment. You can find the respective agency on our website www.vega.com under: "Company - VEGA worldwide" VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 43: Dismounting

    Correct disposal avoids negative effects to persons and environment and ensures recycling of useful raw materials. Materials: see chapter "Technical data" If you have no possibility to dispose of the old instrument professionally, please contact us concerning return and disposal. VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 44: Supplement

    Measuring range up to 5 m (16.4 ft) Liquids Bulk solids up to 2 m (6.562 ft) Dead band 0.25 m (0.82 ft) With inductive load ohmic share min. 25 Ω/mH. VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 45 0.06 %/10 K signal (temperature error) Time to output the correct level (with max. 10 % deviation) after a sudden level change. Incl. non-linearity, hysteresis and non-repeatability. Relating to the nominal measuring range. VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 46 Non-Ex and Ex-d instrument 20 … 72 V DC, 20 … 253 V AC, 50/60 Hz Power consumption max. 4 VA; 2.1 W Tested according to the regulations of German Lloyd, GL directive 2. VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 47 Depending on the version, instruments with approvals can have different technical data. For these instruments, the corresponding approval documents have to be taken into account. These are part of the delivery or can be downloaded under www.vega.com via "VEGA Tools" and "serial number search" as well as via "Downloads" and "Approvals".
  • Page 48: Dimensions

    ") ø 74mm ") Fig. 26: VEGASON 61 Dead zone: 0.25 m (0.82 ft) Measuring range: with liquids up to 5 m (16.4 ft), with solids up to 2 m (6.562 ft) VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 49: Industrial Property Rights

    Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellectuelle. Pour plus d'informations, on pourra se référer au site http://www.vega.com VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad industrial. Para mayor información revise la pagina web http://www.vega.com Линии...
  • Page 50 10 Supplement VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 51 10 Supplement VEGASON 61 • 4 … 20 mA/HART four-wire...
  • Page 52: Information

    All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems correspond to the information avail- able at the time of printing. © VEGA Grieshaber KG, Schiltach/Germany 2008 Subject to change without prior notice 28778-EN-081127...