4.6.3
Terminal strips behind the upper front door
All terminals with reference potential "GND" are connected with one another in the inverter.
Terminals 31, 32
Connection of the optional 24 V supply has the following advantages:
The Control Unit remains in operation after disconnection of the Power Module from the line supply.
•
The Control Unit thus maintains the fieldbus communication, for example.
You can use terminals 51 ... 54 as digital outputs.
•
Power supplies in conformance with SELV (Safety Extra Low Voltage) or PELV (Protective Extra Low
Voltage) are permissible.
If you use a common external power supply for terminals 31, 32 and the digital inputs, you must connect
GND and the reference potential of the digital input ("DI COM1/2/3") with each other.
Terminals 3, 4
You may use the internal 10 V supply or an external power supply for the analog inputs. For an internal
and 10, 11:
10 V supply: Connect AI 0, respectively AI 1- with GND.
Image 4-9
Interconnection example of the digital inputs with external 24 V power supply
Converter with CU250S-2 Control Unit