Hitachi EH-150 Applications Manual page 145

Ethernet module 2 eh-eth2
Hide thumbs Also See for EH-150:
Table of Contents

Advertisement

Task code
H23
Function
Writes the designated number of program steps to the user memory, starting with the designated address.
* For EH-150 CPU, the operation of HI-FLOW programs cannot be performed, while the programs can be transferred.
Execution condition
CPU status
STOP
RUN
×
×
×
Format
Request
H23
(a)
(b)
(a)
Memory area designation (subcommand)
1]
H00: Parameter area (A)
2]
H01: HI-FLOW area *1
3]
H02: HI-LADDER area
4]
H03: Parameter area (B)
(b) User memory address (absolute address)
(c)
Number of steps to be written (H01 to H3C; maximum 60 steps)
(d) Write data (1 step is equivalent to 4 bytes.)
*1: EH-150 does not support HI-FLOW.
Response
(a)
H23
(a)
Response task code (H00 when executed normally)
For task codes other than the normal task codes, refer to the "response list by task code" at the end of this chapter.
Program transfer with address designation
HALT
ERROR
×
×
×
(c)
(d)
Appendix B Task Codes Specifications
READ occupancy
Occupancy
WRITE occupancy
status
B-20
Classification
Memory write

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents