8 Diagnostics and servicing

Sensors
VEGADIS 82
Code
Text message
S003
CRC-error
F014
Sensor input: Short-circuit
F015
Sensor input: Line break
S021
Scaling: Span too small
S022
Scaling: Value too high
F034
EEPROM: CRC error
F035
ROM: CRC error
F037
RAM defective
F040
General hardware error
Reaction when malfunc-
tion occurs
30
8
Diagnostics and servicing
8.1

Maintenance

If the instrument is used correctly, no maintenance is required in
normal operation.
8.2

Asset Management function

The instrument supports the self-monitoring and diagnosis of the con-
nected sensor. Status or failure messages are displayed according to
the sensor via display and adjustment module, PACTware/DTM and
EDD.
You can find a detailed overview of this function in the operating
instructions of the respective sensor.
The following table shows the error codes and text messages of the
VEGADIS 82 and gives information on the cause and removal.
Reason
CRC error during self-
check
Short-circuit or sensor
current > 21 mA
Line break or sensor
current < 3.6 mA
Scaling span too small
Scaling value too high
EEPROM: CRC error
ROM: CRC error
Error of the RAM in the
internal data memory
Hardware error
8.3

Rectify faults

The operator of the system is responsible for taking suitable meas-
ures to rectify faults.
Rectification
Carry out a reset
Send instrument for repair
Check cable
Check sensor
Check cable
Check sensor, probably already in the run-in period
Carry out a fresh scaling, increase the distance
between min. and max. scaling.
Check scaling values and correct, if necessary
Switch the instrument off and on
Carry out reset to default setting
Send instrument for repair
Switch the instrument off and on
Carry out reset to default setting
Send instrument for repair
Switch the instrument off and on
Carry out reset to default setting
Send instrument for repair
Switch the instrument off and on
Carry out reset to default setting
Send instrument for repair
VEGADIS 82 • 4 ... 20 mA