Chapter 5 General Specifications - Mitsubishi Electric Q26UD(E)HCPU User Manual

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

CHAPTER 5
The following table lists the general specifications of the programmable controller.
Item
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
Compliant with
Vibration resistance
JIS B 3502 and
IEC 61131-2
Shock resistance
Operating
atmosphere
*5
Operating altitude
Installation location
Overvoltage
*1
category
*2
Pollution degree
Equipment class
*1
This indicates the section of the power supply to which the equipment is assumed to be connected between the public
electrical power distribution network and the machinery within premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand
level for up to the rated voltage of 300V is 2500V.
*2
This index indicates the degree to which conductive material is generated in terms of the environment in which the
equipment is used.
Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be
expected occasionally.
*3
The storage ambient temperature is -20 to 75°C if the system includes the AnS/A series modules.
*4
The operating ambient humidity and storage ambient humidity are 10 to 90%RH if the system includes the AnS/A series
modules.
*5
Do not use or store the programmable controller under pressure higher than the atmospheric pressure of altitude 0m.
Doing so may cause malfunction. When using the programmable controller under pressure, please consult your local
Mitsubishi Electric representative.
GENERAL SPECIFICATIONS
5 to 95%RH
Under
intermittent
8.4 to 150Hz
vibration
Under continuous
vibration
8.4 to 150Hz
Compliant with JIS B 3502 and IEC 61131-2 (147 m/s

CHAPTER 5 GENERAL SPECIFICATIONS

Specifications
0 to 55°C
*3
-25 to 75°C
*4
, non-condensing
Constant
Frequency
acceleration
5 to 8.4Hz
----
2
9.8m/s
5 to 8.4Hz
----
2
4.9m/s
2
, 3 times each in 3 directions X, Y, Z)
No corrosive gases
0 to 2000m
Inside a control panel
II or less
2 or less
Class I
Half amplitude
Sweep count
3.5mm
10 times each in
X, Y, Z directions
----
1.75mm
----
----
117
5

Hide quick links: