Operation
6.5 Local operation
6.5.8
Bus address
Introduction
The node address of the device on the PROFIBUS, the so-called bus address, is set in
mode 15. The permissible range runs from 0 to 126.
Note
Do not change the bus address of the device while your system is running. The device will
then no longer be visible from the application program.
Procedure
To change the bus address, proceed as follows:
1. Set mode 15.
The currently set bus address of the device appears in the measured value display.
2. Select the bus address within the permissible range.
3. Save with the [M] button.
6.5.9
Device operation type
Introduction
Set the device mode to mode 16.
The device mode [1] is preset on the pressure transmitter. Other device modes are only
suitable if you have set another operation type through PROFIBUS.
Table 6- 17
Display
[0]
[1]
88
Device mode
Meaning
Profile-compliant:
Exchangeable for pressure transmitters with PROFIBUS PA Profile 3.0, with analog input
function block, without totalizer
Delivery state
Profile-compatible with extensions:
Full functionality of the SITRANS P with:
Analog input function block
•
Totalizer
•
SITRANS P DS III/P410 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00053276-08