User-Programmable Self Tests; Control Pushbuttons - GE B90 Instruction Manual

Ur series low impedance bus differential system
Hide thumbs Also See for B90:
Table of Contents

Advertisement

5 SETTINGS
PATH: SETTINGS
PRODUCT SETUP
 USER-PROGRAMMABLE
 SELF TESTS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
All major self-test alarms are reported automatically with their corresponding FlexLogic™ operands, events, and targets.
Most of the minor alarms can be disabled if desired.
When in the "Disabled" mode, minor alarms will not assert a FlexLogic™ operand, write to the event recorder, or display
target messages. Moreover, they will not trigger the
mode, minor alarms continue to function along with other major and minor alarms. Refer to the Relay self-tests section in
chapter 7 for additional information on major and minor self-test alarms.
The
ETHERNET SWITCH FAIL FUNCTION
NOTE
PATH: SETTINGS
PRODUCT SETUP
 CONTROL
 PUSHBUTTON 1
MESSAGE
There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced front
panels. These are user-programmable and can be used for various applications such as performing an LED test, switching
setting groups, and invoking and scrolling though user-programmable displays.
GE Multilin


USER-PROGRAMMABLE SELF TESTS

DIRECT RING BREAK
FUNCTION: Enabled
DIRECT DEVICE OFF
FUNCTION: Enabled
REMOTE DEVICE OFF
FUNCTION: Enabled
PRI. ETHERNET FAIL
FUNCTION: Disabled
SEC. ETHERNET FAIL
FUNCTION: Disabled
BATTERY FAIL
FUNCTION: Enabled
SNTP FAIL
FUNCTION: Enabled
IRIG-B FAIL
FUNCTION: Enabled
ETHERNET SWITCH FAIL
FUNCTION: Disabled
ANY MINOR ALARM
self-test is not applicable to the B90 device.


CONTROL PUSHBUTTONS

CONTROL PUSHBUTTON 1
FUNCTION: Disabled
CONTROL PUSHBUTTON 1
EVENTS: Disabled
B90 Low Impedance Bus Differential System
5.2.11 USER-PROGRAMMABLE SELF TESTS
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
Range: Disabled, Enabled. Valid for units that contain a
CPU with a primary fiber port.
Range: Disabled, Enabled. Valid for units that contain a
CPU with a redundant fiber port.
Range: Disabled, Enabled.
Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
Range: Disabled, Enabled.
Range: Disabled, Enabled. Valid for units that contain a
switch module.
or
messages. When in the "Enabled"
ANY SELF-TEST
5.2.12 CONTROL PUSHBUTTONS
CONTROL PUSHBUTTON 1(7)
Range: Disabled, Enabled
Range: Disabled, Enabled
5.2 PRODUCT SETUP