User-Programmable Self Tests - GE G60 Instruction Manual

Ur series generator management relay
Hide thumbs Also See for G60:
Table of Contents

Advertisement

5 SETTINGS
Table 5–3: RECOMMENDED SETTINGS FOR LED PANEL 2 LABELS
SETTING
PARAMETER
LED 1 Operand
SETTING GROUP ACT 1
LED 2 Operand
SETTING GROUP ACT 2
LED 3 Operand
SETTING GROUP ACT 3
LED 4 Operand
SETTING GROUP ACT 4
LED 5 Operand
SETTING GROUP ACT 5
LED 6 Operand
SETTING GROUP ACT 6
LED 7 Operand
Off
LED 8 Operand
Off
LED 9 Operand
Off
LED 10 Operand
Off
LED 11 Operand
Off
LED 12 Operand
Off
Refer to the Control of Setting Groups example in the Control Elements section of this chapter for group activation.
PATH: SETTINGS
PRODUCT SETUP
USER-PROGRAMMABLE
SELF TESTS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
All major self-test alarms are reported automatically with their corresponding FlexLogic™ operands, events, and targets.
Most of the Minor Alarms can be disabled if desired.
When in the "Disabled" mode, minor alarms will not assert a FlexLogic™ operand, write to the event recorder, display target
messages. Moreover, they will not trigger the
minor alarms continue to function along with other major and minor alarms. Refer to the Relay Self-Tests section in Chapter
7 for additional information on major and minor self-test alarms.
GE Multilin
SETTING
LED 13 Operand
LED 14 Operand
LED 15 Operand
LED 16 Operand
LED 17 Operand
LED 18 Operand
LED 19 Operand
LED 20 Operand
LED 21 Operand
LED 22 Operand
LED 23 Operand
LED 24 Operand

USER-PROGRAMMABLE SELF TESTS

DIRECT RING BREAK
FUNCTION: Enabled
DIRECT DEVICE OFF
FUNCTION: Enabled
REMOTE DEVICE OFF
FUNCTION: Enabled
PRI. ETHERNET FAIL
FUNCTION: Disabled
SEC. ETHERNET FAIL
FUNCTION: Disabled
BATTERY FAIL
FUNCTION: Enabled
SNTP FAIL
FUNCTION: Enabled
IRIG-B FAIL
FUNCTION: Enabled
or
ANY MINOR ALARM
ANY SELF-TEST
G60 Generator Management Relay
5.2 PRODUCT SETUP
PARAMETER
Off
Off
Off
Off
SYNC 1 SYNC OP
SYNC 2 SYNC OP
Off
Off
Off
Off
Off
Off
5.2.11 USER-PROGRAMMABLE SELF TESTS
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
Range: Disabled, Enabled. Valid for units that contain a
CPU with a primary fiber port.
Range: Disabled, Enabled. Valid for units that contain a
CPU with a redundant fiber port.
Range: Disabled, Enabled.
Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
Range: Disabled, Enabled.
messages. When in the "Enabled" mode,
5
5-37