5. PROGRAMMING
Programming
Procedure
0
Initial data setting
32
Writing resolution
65
Writing:
A-D conversion-
enabled/disabled
Averaging proces-
sing designation
98
Reading:
A-D conversion-
completion flag
Digital output
value
1
X000
M0
M1
M10
M2
M12
M3
X001
MOVP K0017 W301
MOVP K0604 W302
MOVP
K50
W305
MOVP K1000 W304
MOVP
K2
W30B
PLS
M0
SET
M1
RST
M3
LEDB RTOP
SUB
H0200
SUB
K20
LEDC W30B
SUB
K1
LEDC
M10
LEDR
SET
M2
RST
M1
LEDB RTOP
SUB
H0200
SUB
K0
LEDC W301
SUB
K5
LEDC
M12
LEDR
SET
M3
RST
M2
LEDB RFRP
SUB
H0200
SUB
K10
LEDC W320
SUB
K10
LEDC
M14
LEDR
5 − 8
MELSEC-A
.... Setting initial data to M → R
link registers
.... Writing resolution setting data
to an A68ADN
.... Writing A-D conversion-
enabled/disabled channels
and averaging processing
designation to the A68AND
after the completion of
writing of resolution setting
data
.... Reading digital output value and
A-D conversion-completion flag
after the completion of initial
setting