Configuring Iec 61850 Proxy Ied - ABB COM600S User Manual

Com600 series 4.1 release iec 61850 proxy server
Hide thumbs Also See for COM600S:
Table of Contents

Advertisement

1MRS757275
3.5.4.
COM600 series, version 4.1
IEC 61850 Proxy Server User's Manual
Table 3.5.3-1 IEC 61850 Proxy Subnetwork properties
Property / Para-
Value or Value range/ Default
meter
Communication
Port
Communication Port
ETH0
ETH1
Default: ETH0
IP Address
Default: 127.0.0.1
Communication
Control
TCP/IP Keepalive
1...3600
Timeout
Default: 15 seconds

Configuring IEC 61850 Proxy IED

Table 3.5.3-1 lists the configurable IEC 61850 Proxy IED object properties and the value
ranges for them. The actual configuration using SAB600 is performed as described in
3.2, Overview of configuration.
Table 3.5.4-1 IEC 61850 Proxy IED properties
Property / Para-
Value or Value range/ Default
meter
Addresses
IP Address
Default: 127.0.0.1
OSI ACSE AE
Default: 23
Qualifier
OSI ACSE AP Title
Default = 1,3,9999,23
Value
OSI Presentation
Default = 00000001
Selector
OSI Session
Default = 0001
Selector
OSI Transport
Default = 0001
Selector
Description
LAN port used by the IEC 61850 protocol
used for GOOSE sending.
Values shown here are default values
when no connection to COM600 has been
made. When the first connection is made
the communication port information is read
from COM600 and the corresponding NIC
value is written to NICInformation property.
Communication channel IP address in
dotted decimal format.
TCP/IP keepalive timeout in seconds.
Description
Communication IP address in dotted
decimal format. (not configurable)
ACSE protocol level configuration para-
meter. AE Qualifier.
ACSE protocol level configuration para-
meter. AP Title.
ACSE protocol level configuration para-
meter. Presentation selector.
ACSE protocol level configuration para-
meter. Session selector.
ACSE protocol level configuration para-
meter. Transport selector.