ABB COM600 3.5 User Manual
ABB COM600 3.5 User Manual

ABB COM600 3.5 User Manual

External opc server
Table of Contents

Advertisement

Quick Links

Station Automation COM600 3.5
External OPC Server User's Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB COM600 3.5

  • Page 1 Station Automation COM600 3.5 External OPC Server User's Manual...
  • Page 3: Table Of Contents

    1MRS757274 Station Automation COM600 3.5 Issued: 30.6.2011 External OPC Server User's Manual Version: A/30.6.2011 Contents: About this manual .................. 5 1.1. Copyrights ..................5 1.2. Trademarks ..................5 1.3. General ..................5 1.4. Document conventions ..............6 1.5. Use of symbols ................7 1.6.
  • Page 4 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual 3.5.8.1. General about configuring data objects for External OPC Device ......... 27 3.5.8.2. Directional protection activation information ..........27 3.5.8.3. Protection activation information (ACT) ..31 3.5.8.4. Analogue set point (APC) ......35 3.5.8.5.
  • Page 5: About This Manual

    In no event shall ABB Oy be liable for direct, indirect, special, incidental, or consequential damages of any nature or kind arising from the use of this document, nor shall ABB Oy be liable for incidental or consequential damages arising from use of any software or hardware described in this document.
  • Page 6: Document Conventions

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Configuration In this section you will find an overview of configuration. You are given instructions on how to configure External OPC Server related objects and the model of a substation or system.
  • Page 7: Use Of Symbols

    Terminology The following is a list of terms associated with COM600 that you should be familiar with. The list contains terms that are unique to ABB or have a usage or definition that is different from standard industry usage. Term...
  • Page 8 A communication protocol developed by Echelon. LON Application Guideline for A proprietary method of ABB on top of the standard LON pro- substation automation; LAG tocol. Series of standards specifications aiming at open connectivity in industrial automation and the enterprise systems that support industry.
  • Page 9: Abbreviations

    LON Application Guideline for substation automation Local Area Network Logical Device LonMark interoperable device communicating in LonWorks network. In this document, the term is used for devices that do not support the ABB LON/LAG communication. Logical Node LON SPA Gateway...
  • Page 10: Document Revisions

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Abbreviation Description SOAP Simple Object Access Protocol Report Control Block URCB Unbuffered Report Control Block eXtended Markup Language 1.8. Document revisions Document version/date Product revision History A/30.6.2011 Document created...
  • Page 11: Introduction

    1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Introduction 2.1. Functional overview The External OPC Server provides methods for connecting data from 3rd party OPC DA server to COM600. overview.jpg Figure 2.1-1 System overview 1. Station Automation Builder 600 (SAB600) 2.
  • Page 12: External Opc Server Features

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual To create a common and protocol independent data interface between the OPC server and client, the process data from the 3rd party OPC server is remodeled using the IEC61850 data modeling in the External OPC Server.
  • Page 13: Configuration

    1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Configuration 3.1. About this section This section guides you in the configuration tasks required before you can start using the External OPC Server. For information on the IEC 61850 data modeling, refer to COM600 User's Manual.
  • Page 14 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Example_view_External_OPC.png Figure 3.2-1 Example view of SAB600 The configuration work can basically be divided into two separate tasks: 1. building an object tree, and 2. configuring object properties. For information on how to enable configuring of OPC item paths in the data objects with SAB600 with the OPC Browser tool, see 3.4, OPC Browser tool.
  • Page 15: Building Object Tree

    1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Object Description External OPC Subnetwork Object representing a physical subnetwork. External OPC IED The IED object presents a physical device in the 3rd party system. External OPC Logical Device (LD) An object representing a group of functions.
  • Page 16: Adding Gateway Object

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual 3.3.2. Adding Gateway object To start building the object tree, add a Gateway object in the Communication structure by selecting the project name, right-click it and select New > Communication > Gate- way.
  • Page 17: Adding Logical Device Objects

    1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual 4. Select the device to import from the drop-down list. You can preview the configur- ation on the right. 5. Click Import. The new preconfigured objects appear in the object tree. If the configuration file is large, the import may take time.
  • Page 18 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual namespace information can be later used to configure the OPC item paths in the data objects with SAB600. 1. Copy the OPC Browser tool to the computer, where the OPC Server is running. The OPC Browser software can be found from the Utilities folder of the installation DVD.
  • Page 19 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Ini_import Figure 3.4-3 External OPC Server Ini Import tool 6. Click Select File in the External OPC Server Ini Import tool to select the file created with the OPC Browser.
  • Page 20 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Control_OPC_item_path_properties Figure 3.4-4 Control OPC Item Path properties 9. A new dialog showing the namespace created with the OPC Browser opens, see Figure 3.4-5. Select the correct OPC item from the tree view and click OK. The path of the selected OPC item will be updated to the property.
  • Page 21: Configuring Objects

    1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual 3.5. Configuring objects 3.5.1. General about configuring objects After the objects have been added, configure the object properties. Figure 3.5.1-1 shows an example of how to use SAB600 to configure the object properties for External OPC Server.
  • Page 22: Configuring External Opc Server Properties

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual 3.5.2. Configuring External OPC Server properties Table 3.5.2-1 External OPC Server properties Property/Parameter Value or Value range/Default Description Source OPC Server ProgID Defines the ProgID of the mapped server. Remote Node Name...
  • Page 23: Configuring Logical Device Properties

    1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Name Value or Value range/ Default Description Station/Remote OPC path of the station remote switch Switch OPC Path position to be used with this logical device. The format is Node#ProgID For OPC...
  • Page 24: Configuring Data Objects For Internal Opc Data

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Parameter Value or Value range/ Default Description Logical Node Class ANCR, ARCO, ATCC, AVCO, Logical node class LPHD, CALH, CCGR, CILO, CPOW, CSWI, GAPC, GGIO, GSAL, IARC, IHMI, ITCI, ITMI,...
  • Page 25: Integer Status (Ins)

    1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual 3.5.7.2. Integer status (INS) Table 3.5.7.2-1 Property/Para- Value or Value range/ Default Description meter Basic Common Data Common data class according to IEC Class 61850 Addresses Item Tag Path Default: None Item tag path for the internal status information.
  • Page 26: Controllable Single Point (Spc) For Opc Internal Data

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter Item Tag Path Item tag path for the internal status information. The internal server tags that can be used are located in the Attributes nodes that are located under the root, line, and IED nodes.
  • Page 27: Configuring Data Objects For External Opc Client

    1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual 3.5.8. Configuring data objects for External OPC Client 3.5.8.1. General about configuring data objects for External OPC Device Use the OPC Browser tool to configure the OPC item paths in the data objects with SAB600. For more information, see 3.4, OPC Browser tool.
  • Page 28 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Update Rate 0 to 65535 Defines the requested shortest interval in milliseconds at which the source OPC Default: 0 server should report that an OPC item’s value has changed.
  • Page 29 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example General Bitmask BITMASK_OR Defines the type if used bitmask for Gen- Type eral BITMASK_AND BITMASK_XOR BITMASK_BOOL_ALL BITMASK_BOOL_NONE BITMASK_BOOL_ANY BITMASK_BOOL_ANYNOT- BITMASK_BOOL_SOMENOT- BITMASK_BOOL_ONLY...
  • Page 30 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Phase A Bitmask 0 to 65535 Bitmask for phase A Default: 0 Phase A Bitmask BITMASK_OR Defines the type of bitmask used for Phase...
  • Page 31: Protection Activation Information (Act)

    1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Phase B OPC Item OPC item path for phase B Path Phase C Bitmask 0 to 65535 Bitmask for phase C...
  • Page 32 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example General OPC Item OPC item path for general phase Path Neutral OPC Item OPC item path for neutral phase Path Phase A OPC Item...
  • Page 33 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example General OPC Item OPC item path for general phase Path Neutral Bitmask 0 to 65535 Bitmask for neutral Default: 0 Neutral Bitmask...
  • Page 34 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Phase A Bitmask BITMASK_OR Defines the type of bitmask used for Phase Type BITMASK_AND BITMASK_XOR BITMASK_BOOL_ALL BITMASK_BOOL_NONE BITMASK_BOOL_ANY BITMASK_BOOL_ANYNOT- BITMASK_BOOL_SOMENOT- BITMASK_BOOL_ONLY...
  • Page 35: Analogue Set Point (Apc)

    1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Phase C Bitmask 0 to 65535 Bitmask for phase C Default: 0 Phase C Bitmask BITMASK_OR Defines the type of used bitmask for Phase...
  • Page 36: Binary Counter Reading (Bcr)

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Input Scale Lookup Table Scale Scale for input signal Stepwise Linear Scale Default: None 3.5.8.5. Binary counter reading (BCR) Table 3.5.8.5-1 Configurable BCR properties for External OPC clients...
  • Page 37 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Subtype Basic Object subtype Update Rate 0 to 65535 Defines the requested shortest interval in milliseconds at which the source OPC Default: 0 server should report that an OPC item’s...
  • Page 38: Complex Measured Value (Cmv)

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Lower Control Scale Lookup Table Scale Scale for lower control Stepwise Linear Scale Default: None Scale Lookup Table Scale Scale for indication signal...
  • Page 39 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Scale Ang Lookup Table Scale Scale for angle Stepwise Linear Scale Default: None Scale Mag Lookup Table Scale Scale for magnitude...
  • Page 40 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Table 3.5.8.7-2 Configurable CMV properties for External OPC clients, subtype LIMIT_CHECK Property/Para- Value or Value range/ Default Description meter /Example Basic 61850-Type 61850-Type Angle OPC Item OPC item path for angle...
  • Page 41 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Unit meter, kilogram, second, Unit for measurement ampere, kelvin, mole, candela, degrees, radian, steradian, gray (J/Kg), becquerel (l/s), degrees Celsius), sievert...
  • Page 42: Delta (Del)

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual 3.5.8.8. Delta (DEL) Table 3.5.8.8-1 Configurable DEL properties for External OPC clients, subtype Basic Property/Para- Value or Value range/ Default Description meter /Example Basic 61850-Type 61850-Type V ab Angle OPC...
  • Page 43 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Unit meter, kilogram, second, Unit for measurement ampere, kelvin, mole, candela, degrees, radian, steradian, gray (J/Kg), becquerel (l/s), degrees Celsius), sievert...
  • Page 44 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example V ab Magnitude OPC item path for ab V magnitude OPC Item Path V bc Angle OPC OPC item path for bc V angle...
  • Page 45 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Unit meter, kilogram, second, Unit for measurement ampere, kelvin, mole, candela, degrees, radian, steradian, gray (J/Kg), becquerel (l/s), degrees Celsius), sievert...
  • Page 46: Controllable Double Point (Dpc)

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual 3.5.8.9. Controllable double point (DPC) Table 3.5.8.9-1 Configurable DPC properties for External OPC Clients, subtype Basic Property/Para- Value or Value range/ Default Description meter /Example Basic 61850-Type 61850-Type Cancel OPC Item...
  • Page 47 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Open Execute Scale Lookup Table Scale Scale for open execute Stepwise Linear Scale Default: None Open Select Scale Lookup Table Scale...
  • Page 48: Device Name Plate (Dpl)

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Update Rate 0 to 65535 Defines the requested shortest interval in milliseconds at which the source OPC Default: 0 server should report that an OPC item’s value has changed.
  • Page 49: Double Point Status (Dps)

    1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example 61850-Type 61850-Type HW Revision OPC OPC item path for HW revision Item Path Location OPC Item OPC item path for location...
  • Page 50: Controllable Integer Status (Inc)

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Table 3.5.8.11-2 Configurable DPS properties for External OPC clients, subtype OPEN_CLOSED_ITEMS Property/Para- Value or Value range/ Default Description meter /Example Basic 61850-Type 61850-Type Closed OPC Item OPC item path for closed...
  • Page 51: Integer Status (Ins)

    1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Scale and Unit Control Scale Lookup Table Scale Scale for control signal Stepwise Linear Scale Default: None Scale Lookup Table Scale...
  • Page 52: Logical Node Name Plate (Lpl)

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Control OPC Item OPC item path for control Path State OPC Item OPC item path for state Path Sub Type Basic...
  • Page 53: Measured Value (Mv)

    1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual 3.5.8.16. Measured value (MV) Table 3.5.8.16-1 Configurable MV properties for External OPC clients, subtype Basic Property/Para- Value or Value range/ Default Description meter /Example Basic 61850-Type 61850-Type Magnitude OPC OPC item path for magnitude...
  • Page 54 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Unit meter, kilogram, second, Unit for measurement ampere, kelvin, mole, candela, degrees, radian, steradian, gray (J/Kg), becquerel (l/s), degrees Celsius), sievert...
  • Page 55 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Sub Type LIMIT_CHECK Object subtype Update Rate 0 to 65535 Defines the requested shortest interval in milliseconds at which the source OPC Default: 0 server should report that an OPC item’s...
  • Page 56 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Unit meter, kilogram, second, Unit for measurement ampere, kelvin, mole, candela, degrees, radian, steradian, gray (J/Kg), becquerel (l/s), degrees Celsius), sievert...
  • Page 57: Controllable Single Point (Spc)

    1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual 3.5.8.17. Controllable single point (SPC) Table 3.5.8.17-1 Configurable SPC properties for External OPC clients, subtype Basic Property/Para- Value or Value range/ Default Description meter /Example Basic 61850-Type 61850-Type Control OPC Item...
  • Page 58: Single Point Status (Sps)

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Update Rate 0 to 65535 Defines the requested shortest interval in milliseconds at which the source OPC Default: 0 server should report that an OPC item’s value has changed.
  • Page 59 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example 61850-Type 61850-Type Bitmask Type BITMASK_OR Defines the type of used bitmask BITMASK_AND BITMASK_XOR BITMASK_BOOL_ALL BITMASK_BOOL_NONE BITMASK_BOOL_ANY BITMASK_BOOL_ANYNOT- BITMASK_BOOL_SOMENOT- BITMASK_BOOL_ONLY BITMASK_BOOL_EXACTLY Default: BITMASK_OR...
  • Page 60: Wye

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual 3.5.8.19. Table 3.5.8.19-1 Configurable WYE properties for External OPC clients, subtype Basic Property/Para- Value or Value range/ Default Description meter /Example Basic 61850-Type 61850-Type I a Angle OPC Item OPC item path for a I angle...
  • Page 61 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Net Multiplier yocto, zepto, atto, femto, pico, Multiplier for net nano, micro, milli, centi, deci, deka, hecto, kilo, mega, giga, tera, peta, exa, zetta, yotta...
  • Page 62 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Net Unit dimensioless, meter, kilogram, Unit for net second, ampere, kelvin, mole, candela, degrees, radian, steradian, gray (J/Kg), becquerel (l/s), degrees...
  • Page 63 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Neutral Scale Mag Lookup Table Scale Scale for neutral magnitude Stepwise Linear Scale Default: None Neutral Unit See Net Unit Unit for neutral...
  • Page 64 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Res Max Limit 20000 Max limit for res Res Min Limit Min limit for res Table 3.5.8.19-2 Configurable WYE properties for External OPC clients, subtype...
  • Page 65 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Net Multiplier yocto, zepto, atto, femto, pico, Multiplier for net nano, micro, milli, centi, deci, deka, hecto, kilo, mega, giga, tera, peta, exa, zetta, yotta...
  • Page 66 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Net Unit dimensioless, meter, kilogram, Unit for net second, ampere, kelvin, mole, candela, degrees, radian, steradian, gray (J/Kg), becquerel (l/s), degrees...
  • Page 67 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Phase Multiplier See Net Multiplier Multiplier for phase Phase Number Of 0 to 9 Number of decimals for phase Decimals Default: 0...
  • Page 68: Configuring Dcom

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Property/Para- Value or Value range/ Default Description meter /Example Neutral Max Limit 20000 Max limit for neutral Neutral Min Limit Min limit for neutral Phase Hi Limit Hi limit for phase...
  • Page 69 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual To configure DCOM: 1. Select My Computer Properties > Default Properties. 2. Select the Enable Distributed COM on this computer check box. Default Properties.jpg Figure 3.6.1-1 Default Properties See the following illustrations for information on the DCOM configuration settings.
  • Page 70 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Launch_permission_Limits_Administrators.jpg Figure 3.6.1-2 Administrator Permission Limits...
  • Page 71 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Launch permission Defaults Administrators.jpg Figure 3.6.1-3 Launch permission Defaults Administrators...
  • Page 72 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Launch permission Limits Everyone.jpg Figure 3.6.1-4 Launch permission Limits Everyone...
  • Page 73 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Access permission Defaults Self.jpg Figure 3.6.1-5 Access permission Defaults Self...
  • Page 74 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Access permission Security Limits Everyone.jpg Figure 3.6.1-6 Access permission Security Limits Everyone...
  • Page 75 1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Access permission Security Limits Anonymous.jpg Figure 3.6.1-7 Access permission Security Limits Anonymous If the server computer is running on Windows XP, the default installation for XP forces remote users to authenticate as Guest.
  • Page 76: Operation

    Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Operation 4.1. About this section This section describes the basic operation procedures you can carry out after the been configured. After this, you can, for example, monitor and control the condition of connections in network.
  • Page 77: Data Object Diagnostics

    1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Ext_Event_log_file.png Figure 4.3-2 Event log file Diagnostic AE Client Diagnostic events can be monitored and controlled using the Diagnostic AE Client function. Click Refresh to update the status information. To be able to receive events from a certain device, diagnostic events must be enabled for this respective device.
  • Page 79: Index

    1MRS757274 Station Automation COM600 3.5 External OPC Server User's Manual Index adding Data object ..................... 17 Gateway object ....................16 Logical device ....................17 Logical node ....................17 OPC Server object ..................16 configuring object ......................21 Controllable single point (SPC) properties .......................
  • Page 80 Station Automation COM600 3.5 1MRS757274 External OPC Server User's Manual Logical device adding ......................17 Logical Device properties ....................... 23 Logical node adding ......................17 properties ....................... 23 object configuring ..................... 21 object tree building ......................15 OPC Server object adding ......................
  • Page 82 Contact us ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, FINLAND Tel. +358 10 22 11 Fax. +358 10 224 1094 ABB Inc. Distribution Automation 655 Century Point Lake Mary, FL 32746, USA Tel: +1 407 732 2000 Fax: +1 407 732 2335...

Table of Contents