22
COM600 series, version 4.1
IEC 61850 Proxy Server User's Manual
Property/Parameter
Buffered
Configuration Revision
Data Set
Indexed
Integrity period
Report ID
Option Fields
Config Reference
Data Ref
Value or value range/Default
True
False
Default: True
0...2147483647
True
False
Default: True
0...214748647
Default: 0
True
False
Default: False
True
False
Default: False
1MRS757275
Description
Controls if the RCB is buffered
or unbuffered.
Configuration revision of the
data set referenced by this
RCB. Every modification in the
data set increases the Configur-
ation Revision property by one.
The name of the data set to be
sent by the report control block.
Indicates if this RCB is con-
figured with indexed naming
convention.
Integrity period in milliseconds.
If this attribute has a value > 0
ms, an integrity report with all
data listed in the data set is
sent periodically in this interval.
By default, this feature is not
enabled, because it generates
an unnecessary load to the
server and network. If this fea-
ture is used, the Trigger Option
'Period' in RCB needs to be
enabled. Configurable.
Used as identification in
information reports to specify
that the report is from this RCB.
By default report control block
MMS path name is used. Con-
figurable.
Defines what information is
sent with the information report.
Configurable.