Func.
Name
Code
A012
[O] input active range
end frequency
A013
[O] input active range
start voltage
A014
[O] input active range
end voltage
A015
[O] input start frequency
enable
A016
Analog input filter
A017
EzSQ function select
a019
Multi-speed operation
selection
A020
Multi-speed freq. 0
A220
Multi-speed freq. 0,
nd
2
motor
A021
Multi-speed freq. 1 to
15
to
A035
(for both motors)
A038
Jog frequency
"A" Function
Description
The output frequency
corresponding to the analog
input range ending point,
range is 0.00 to
*1
400.0(580.0)
The starting point (offset) for
the active analog input range,
range is 0. to 100.
The ending point (offset) for
the active analog input range,
range is 0. to 100.
Two options; select codes:
00...Use offset (A011 value)
01...Use 0Hz
Range n = 1 to 31,
1 to 30 : ×2ms filter
31: 500ms fixed filter with ±
0.1kHz hysteresis.
Select codes:
00...Disable
01...Activate by PRG terminal
02...Activate always
Select codes:
00...Binary operation (16
speeds selectable with 4
terminals)
01...Bit operation (8 speeds
selectable with 7
terminals)
Defines the first speed of a
multi-speed profile, range is
0.00 / start frequency to
*1
400(580)
Hz
A020 = Speed 0 (1st motor)
Defines the first speed of a
multi-speed profile or a 2nd
motor, range is 0.00 / start
frequency to 400(580)
A220 = Speed 0 (2nd motor)
Defines 15 more speeds,
range is 0.00 / start frequency
*1
to 400(580)
A021=Speed 1 to
A035=Speed15
Defines limited speed for jog,
range is from start frequency
to 9.99 Hz
A
*1
Hz
Hz.
57
Defaults
B
Initial data
0.00
0.
100.
01
8.
00
00
6.0
6.0
0.0
6.00
Units
Hz
%
%
Spl.
Hz
Hz
Hz
Hz

Hide quick links: