Frequency arrival output [FA1] uses the
standard output frequency (parameter
F001) as the threshold for switching. In
the figure to the right, Frequency Arrival
[FA1]
turns
ON
frequency gets within Fon Hz below or
Fon Hz above the target constant
frequency, where Fon is 1% of the set
maximum frequency and Foff is 2% of
the
set
maximum
provides hysteresis that prevents output
chatter near the threshold value. The
hysteresis effect causes the output to
turn ON slightly early as the speed
approaches the threshold. Then the
turn-OFF point is slightly delayed. Note
the active low nature of the signal, due to
the open collector output.
Frequency
arrival
works the same way; it just uses two
separate thresholds as shown in the
figure to the right. These provide for
separate acceleration and deceleration
thresholds to provide more flexibility than
for [FA1]. [FA2/FA4] uses
during acceleration for the ON threshold,
C043/C046
and
during deceleration for the
OFF threshold. This signal also is active
low. Having different accel and decel
thresholds provides an asymmetrical
output function. However, you can use
equal ON and OFF thresholds, if desired.
As for [FA3/FA5] signal, the basic
meaning of "Fon/Foff" is the same as
above.
And,
"C042/C045
and
correlated with [FA2/FA4] signal.
Basically, the meaning of "Fon/Foff" in this
case is the same as above examples, but
there are slight differences from the usage
of [FA2/FA4] signal.
In acceleration status, [FA3/FA5] signal
becomes ON from ("C042/C045" - "Fon") to
("C042/C045" + "Foff").
In deceleration status, [FA3/FA5] signal
becomes ON from ("C043/C046" + "Fon")
to ("C043/C046" - "Foff").
There is no [FA3/FA5] between "ONs" in
the figure, because frequency arrival
output is out of the area defined by the
when
the
output
frequency.
This
output
[FA2/FA4]
C042/C045
C043/C046
are
43
Output
Fon
freq.
Fon
0
FA1
ON
signal
Fon=1% of max. frequency
Foff=2% of max. frequency
Output
freq.
thresholds
C042/C045
C043/C046
0
FA2/FA4
signal
Fon=1% of max. frequency
Foff=2% of max. frequency
Output
freq.
Foff
thresholds
Fon
C042/C045
C043/C046
0
FA3/FA5
ON
signal
Fon=1% of max. frequency
Foff=2% of max. frequency
F001
Foff
F001
Foff
ON
Fon
Foff
ON
Fon
Foff
ON