COM600 series, Version 4.1
External OPC Server User's Manual
Property/Parameter
Logical Node Class
Logical Node Instance
Logical Node Prefix

Configuring data objects for Internal OPC Data

General about configuring data objects for Internal OPC Data

Internal data objects describe internal status information of an OPC server, for example
whether the connection between the External OPC Server and the device (IED) is
working or not. When internal information of an OPC server needs to be transferred,
that is information that does not originate from a device, to an OPC Client, virtual data
objects must be created.
The External OPC Server supports three internal data object types that provide status
information:
3.5.7.2, Integer status (INS)
3.5.7.3, Single point status (SPS)
3.5.7.4, Controllable single point (SPC) for OPC internal data
Value or Value range/ Default
ANCR, ARCO, ATCC, AVCO,
LPHD, CALH, CCGR, CILO,
CPOW, CSWI, GAPC, GGIO,
GSAL, IARC, IHMI, ITCI, ITMI,
MDIF, MHAI, MHAN, MMTR,
MMXN, MMXU, MSQI, MSTA,
PDIF, PDIR, PDIS, PDOP,
PDUP, PFRC, PHAR, PHIZ,
PIOC, PMRI, PMSS, POPF,
PPAM, PSCH, PSEF, PTEF,
PTOC, PTOF, PTOV, PTRC,
PTTR, PTUC, PTUV, PUPF,
PTUF, PVOC, PVPH, PZSU,
RDRE, RADR, RBDR, RDRS,
RBRF, RDIR, RFLO, RPSB,
RREC, RSYN, SARC, SIMG,
SIML, SPDC, XCBR, XSWI,
TCTR, TVTR, YEFN, YLTC,
YPSH, YPTR, ZAXN, ZBAT,
ZBSH, ZCAB, ZCAP, ZCON,
ZGEN, ZGIL, ZLIN, ZMOT,
ZREA, ZRRC, ZSAR, ZTCF,
ZTCR
Default: GGIO
LN Inst Range is from 1 -
2147483647
Default: None
1MRS757274
Description
Logical node class
Logical node instance number
Prefix for logical node