5.3

Diagnostic messages

A diagnostics alarm is generated and the DIAG-LED flashes on the module for each
diagnostics event. You can read out the diagnostics alarms, for example, in the diagnostics
buffer of the CPU. You can evaluate the error codes with the user program.
Note
Parallel connection of two outputs
For parallel connection of two outputs for redundant control of a load, the channel
diagnostics "Short-circuit to L+" and "Wire break" must be deactivated.
Table 5- 4
Diagnostics alarms, their meaning and corrective measures
Diagnostics alarm
Error code
Short-circuit
1
H
Wire break
6
H
Parameter assign-
10
ment error
Supply voltage
11
missing
Channel temporarily
1F
unavailable
Digital output module DQ 16x24VDC/0.5A ST (6ES7132-6BH00-0BA0)
Manual, 12/2015, A5E03574420-AC
Meaning
Short-circuit of actuator supply to
ground
Short-circuit of actuator supply to L+
Actuator circuit impedance too high
Wire break between the module and
actuator
Channel not connected (open)
The module cannot evaluate param-
H
eters for the channel.
Incorrect parameter assignment.
Missing or insufficient supply voltage L+
H
Firmware update is currently in progress
H
or has been canceled. The module does
not output any process or substitute
values in this state.
Interrupts/diagnostic alarms
5.3 Diagnostic messages
Solution
Correct the process wiring
Use a different actuator type or modify the
wiring, e.g. use cables with larger cross-
section
Connect the cable
Disable diagnostics
Connect a resistor to the actuator con-
tacts in the load resistance range
Correct the parameter assignment
Check supply voltage L+ on the
BaseUnit
Check BaseUnit type
Wait for firmware update.
Restart the firmware update.
21