3A.1 Related documents 7.12 Fault finding 3A.2 Location of appliance 3A.3 Gas supply Wiring diagrams Page 3A.4 Flue system Installation of Vokera time clock 3A.5 Air supply External controls important 3A.6 Water circulation 3A.7 Electrical supply Exploded diagrams Page 3A.8 Mounting on a combustible surface Table 1 3A.9 Timber framed buildings...
Page 3
Vokera twin flue system. pass. This appliance is designed primarily for use with sealed Pinnacle is produced as a room sealed, category C1, C3, systems; however it can also be used on an open vented C6 appliance, suitable for wall mounting applications system, provided that the necessary installation only.
SECTION 1 DESIGN PRINCIPLES AND OPERATING SEQUENCE PRINCIPLE COMPONENTS differential is inverted; a fan speed sensor that checks the correct A fully integrated electronic control board operation of the fan, thereby allowing safe featuring differential temperature control, operation of the burner; continuous air/gas modulation, anti-cycle a condense pressure switch that will stop the control, pump over-run, self-diagnostic fault...
2.12 PUMP DUTY Fig. 3 shows the flow rate available – after allowing for pressure loss through the appliance – for system requirements. When using this graph apply only the pressure loss of the system. The graph is based on 20 ºC temperature differential. 1000 1100 1200...
This appliance must be installed by a competent GAS SUPPLY person in accordance with the Gas Safety (Instal- The gas meter – as supplied by the gas supplier lation & Use) Regulations. – must be checked to ensure that it is of adequate size to deal with the maximum rated input of all RELATED DOCUMENTS the appliances that it serves.
3.11 INHIBITORS mounted in a position at least 1 metre above the Vokera recommend that a inhibitor – suitable for highest point in the system and at least 5 metres use with aluminium heat exchangers – is used to above the boiler (fig. 5A). The cold feed from the...
Page 9
*Fernox and Sentinel manufacture products that have proved suitable for use with Vokera appliances. Vokera Ltd. cannot comment on the suitability of any other such product with our appliances. CH return valve Gas cock CH flow valve Fig. 6 CONDENSATE...
SECTION 3A GENERAL REQUIREMENTS (EIRE) This appliance must be installed by a competent 3A.4 FLUE SYSTEM person in accordance with and defined by, the The terminal should be located where the dispersal Standard Specification (Domestic Gas of combustion products is not impeded and with Installations) Declaration (I.S.
3A.11 INHIBITORS generally this is sufficient, however if the system Vokera recommend that a inhibitor – suitable for has an unusually high water content, it may be use with aluminium heat exchangers – is used...
Once the bracket has been secured to the wall, alternatively, the Vokera twin flue system can be mount the appliance onto the bracket. utilised if longer flue runs are required.
Page 13
NOTE adaptor and insert the concentric flue pipe into the flue bend ensuring the correct seal is made. When cutting an extension to the required length, you must ensure that the excess is cut from the plain end of the extension (fig. 7 & 7B). Remove any burrs, and check that all seals are located properly.
Page 14
4.5.3 TWIN FLUE SYSTEM Remove the blanking plates (located to the left The Vokera twin flue system enables greater flue of the appliance flue outlet) and – using the distances to be achieved (see section 2.9) than same screws – install the air baffle (A).
connects to the exhaust connection on the The convertor box on the vertical terminal will concentric to twin converter. have to be temporarily removed when inserting If necessary cut the plain ends (male) of the twin the terminal through the flashing. flue pipes to allow connection to the concentric to twin converter.
(condensate outlet pipe) is connected to the screws outlet of the trap. The flexible pipe must be connected to a plastic waste pipe only. The plastic waste pipe must have a minimum of a 3º fall towards the drain. Any external run of pipe should be insulated to prevent the risk of freezing.
4.10 CASING REMOVAL Lower the front control panel as described in section 4.9.1. Locate and remove the 2 screws that secure the controls fascia to the appliance casing (fig. 13A) locate and remove the 2 screws that secure the casing to the back frame of the boiler (fig. 15) gently pull one side of the casing then the other to disengage it from the retaining clips lift the casing upward to disengage it from the...
*Both Sentinel and Fernox manufacture products and/or debris that are residual from the installation that have proved suitable for use with Vokera of the system, consequently it is essential that the appliances. Vokera Ltd. cannot comment on the...
Step number Information displayed Press the buttons at the same Temperature at flow sensor time to return to the normal operating mode. Temperature at return sensor Isolate the appliance from the electrical supply, Unused Unused remove the manometer from the inlet test nipple, Unused tighten the test nipple screw, and check for Required temperature (as set at parameter 4)
It is the law that any servicing work is carried out remove the four Allen screws that hold the pump by competent person such as a Vokera engineer, in position, pull firmly on the pump head to release an approved service agent, British Gas or other it from the base.
NTC THERMISTORS (temperature sensors) Carry out component removal procedure as de- scribed in section 6.4. Flow & return sensors (fig. 1 & 18) Pull back protective boot and remove the 2 spade connectors. Slacken and remove the 2 securing screws. Replace in the reverse order.
6.14 ELECTRODE (fig. 21 & 22) Carry out component removal procedure as de- Inlet connection scribed in section 6.4. Pressure Unclip and remove the air chamber cover. switch connection Remove the electrode lead. Remove the 2 screws that secure the electrode to the combustion cover, and gently withdraw the electrode.
SECTION 7 CHECKS, ADJUSTMENTS AND FAULT FINDING CHECKING APPLIANCE OPERATION and S press and hold the mode buttons When carrying out any repairs or servicing to the simultaneously for 2 seconds; appliance, the relevant commissioning and/or set-up procedure must be undertaken to ensure when “COdE”...
Page 25
Service parameters must only be changed or adjusted by qualified service personnel Parameter Description Range Factory setting Factory setting New setting Pinnacle 16 Pinnacle 26 5 °C - 60° C 20 °C Minimum setting for flow sensor 20° C Unused...
Code Reason E 00 False flame Maximum E 02 No flame detected screw E 03 Internal fault (PCB) E 04 Appliance lockout and power failure E 05 Internal fault (PCB) E 06 Internal fault (PCB) E 07 Internal fault (PCB) E 11 Internal fault (PCB) E 13...
7.10 EXTERNAL FAULTS the isolator, re-check wiring and connections Before carrying out any fault-finding or component between the isolator and the appliance. replacement, ensure the fault is not attributable If tests on the isolator also reveal reversed polarity to any aspect of the installation. or a supply fault, consult the local electricity For example, external wiring fault, service valves supplier for advice.
Room thermostat contact rated at 230V ° (part n 201 or 202) The Vokera time clock (part no. 201 & 202) can be installed using the following procedure: • Isolate the appliance from the electrical supply and remove the casing as described in 4.9.1.
Page 34
“Y” plan system Room thermostat contact rated at 230V Fig. 32A...
Page 35
FUNCTIONAL DIAGRAM Fig. 33 L2 (R) Led alarm R.T. Room thermostat Fuse 2 AF Pump Fuse 4 AT Flow thermistor (NTC) S/S.E. Spark/sense electrode Return thermistor (NTC) Gas valve solenoids BE05 Connection board P.S. Pressure switch (NC) MCBA Control board L2 (V) Led OK...
Page 41
POS. DESCRIPTION Main burner jet 8897 9295 Roomsealed chamber 10023486 10023486 Main burner jet LPG 10022453 8970 Upper panel for air box 8881 8881 Washer 9299 9299 Main burner jet support 1195 1195 Air box hole cap 8084 8084 Main burner 1196 1196 Air conveyor...
SECTION 10 L.P.G. INSTRUCTIONS For details of converting boilers to LPG please refer to the instructions supplied with the relevant conversion kit. 10.1 TECHNICAL DATA Inlet pressure 37 mbar 37 mbar Gas rate (max.) 2.49 l/per hr. 4.08 l/per hr. Gas rate (min.) 0.72 l/per hr.
Need help?
Do you have a question about the pinnacle and is the answer not in the manual?
Questions and answers