5 SETTINGS
Table 5–26: GOOSE ANALOG INPUT BASE UNITS (Sheet 2 of 2)
ELEMENT
SOURCE CURRENT
SOURCE POWER
SOURCE VOLTAGE
The GOOSE analog input FlexAnalog values are available for use in other B30 functions that use FlexAnalog values.

PATH: SETTINGS
INPUTS/OUTPUTS
 GOOSE UINTEGER
 INPUT 1
MESSAGE
The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger values between any two UR-series
devices. The following settings are available for each GOOSE uinteger input.
UINTEGER 1 DEFAULT: This setting specifies the value of the GOOSE uinteger input when the sending device is
offline and the
UINTEGER 1 DEFAULT MODE
number.
UINTEGER 1 DEFAULT MODE: When the sending device is offline and this setting is "Last Known", the value of the
GOOSE uinteger input remains at the last received value. When the sending device is offline and this setting value is
"Default Value", then the value of the GOOSE uinteger input is defined by the
The GOOSE integer input FlexInteger values are available for use in other B30 functions that use FlexInteger values.
GE Multilin
BASE UNITS
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
P
= maximum value of V
BASE
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE

IEC 61850 GOOSE UINTEGERS
UINTEGER
1 DEFAULT:
1000
UINTEGER
1 DEFAULT
MODE: Default Value
is set to "Default Value".This setting is stored as a 32-bit unsigned integer
B30 Bus Differential System
5.8 INPUTS AND OUTPUTS
× I
for the +IN and –IN inputs
BASE

5.8.13 IEC 61850 GOOSE INTEGERS


GOOSE UINTEGER INPUT 1(16)
Range: 0 to 429496295 in steps of 1
Range: Default Value, Last Known
UINTEGER 1 DEFAULT
5
setting.