5.6 GROUPED ELEMENTS
SETTING
GROUND IOC1
FUNCTION:
Enabled = 1
SETTING
GROUND IOC1
SOURCE:
IG
SETTING
GROUND IOC1
BLOCK:
Off = 0

PATH: SETTINGS
GROUPED ELEMENTS
 BREAKER FAILURE 1
5
5-148
SETTING
GROUND IOC1
PICKUP:
AND
RUN
IG
Figure 5–59: GROUND IOC1 SCHEME LOGIC
SETTING GROUP 1(6)
BF1 FUNCTION:
Disabled
BF1 MODE:
MESSAGE
3-Pole
BF1 SOURCE:
MESSAGE
SRC 1
BF1 USE AMP SUPV:
MESSAGE
Yes
BF1 USE SEAL-IN:
MESSAGE
Yes
BF1 3-POLE INITIATE:
MESSAGE
Off
BF1 BLOCK:
MESSAGE
Off
BF1 PH AMP SUPV
MESSAGE
PICKUP: 1.050 pu
BF1 N AMP SUPV
MESSAGE
PICKUP: 1.050 pu
BF1 USE TIMER 1:
MESSAGE
Yes
BF1 TIMER 1 PICKUP
MESSAGE
DELAY: 0.000 s
BF1 USE TIMER 2:
MESSAGE
Yes
BF1 TIMER 2 PICKUP
MESSAGE
DELAY: 0.000 s
BF1 USE TIMER 3:
MESSAGE
Yes
BF1 TIMER 3 PICKUP
MESSAGE
DELAY: 0.000 s
BF1 BKR POS1 φA/3P:
MESSAGE
Off
B30 Bus Differential System
SETTINGS
GROUND IOC1 PICKUP
DELAY:
GROUND IOC1 RESET
DELAY:
t
PKP
PICKUP
t
RST


BREAKER FAILURE

Range: Disabled, Enabled
Range: 3-Pole, 1-Pole
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: Yes, No
Range: Yes, No
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0.001 to 30.000 pu in steps of 0.001
Range: 0.001 to 30.000 pu in steps of 0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic operand
5 SETTINGS
FLEXLOGIC OPERANDS
GROUND IOC1 PKP
GROUND IOIC DPO
GROUND IOC1 OP
827037A5.VSD
5.6.7 BREAKER FAILURE
BREAKER FAILURE 1(6)