Teleprotection Inputs And Outputs - GE B30 UR Series Instruction Manual

Bus differential system
Hide thumbs Also See for B30 UR Series:
Table of Contents

Advertisement

5.8 INPUTS AND OUTPUTS
a) OVERVIEW
The relay provides sixteen teleprotection inputs on communications channel 1 (numbered 1-1 through 1-16) and sixteen
teleprotection inputs on communications channel 2 (on two-terminals two-channel and three-terminal systems only, num-
bered 2-1 through 2-16). The remote relay connected to channels 1 and 2 of the local relay is programmed by assigning
FlexLogic operands to be sent via the selected communications channel. This allows the user to create distributed protec-
tion and control schemes via dedicated communications channels. Some examples are directional comparison pilot
schemes and direct transfer tripping. It should be noted that failures of communications channels will affect teleprotection
functionality. The teleprotection function must be enabled to utilize the inputs.
b) TELEPROTECTION INPUTS

PATH: SETTINGS
INPUTS/OUTPUTS
 TELEPROT INPUTS
5
Setting the
TELEPROT INPUT ~~ DEFAULT
defaults the input to logic 0 when the channel fails.
The "Latest/On" and "Latest/Off" values freeze the input in case of lost communications. If the latest state is not known,
such as after relay power-up but before the first communication exchange, then the input defaults to logic 1 for "Latest/On"
and logic 0 for "Latest/Off".
5-200

TELEPROTECTION
TELEPROT INPUT 1-1
DEFAULT: Off
TELEPROT INPUT 1-2
MESSAGE
DEFAULT: Off
TELEPROT INPUT 1-16
MESSAGE
DEFAULT: Off
TELEPROT INPUT 2-1
MESSAGE
DEFAULT: Off
TELEPROT INPUT 2-2
MESSAGE
DEFAULT: Off
TELEPROT INPUT 2-16
MESSAGE
DEFAULT: Off
setting to "On" defaults the input to logic 1 when the channel fails. A value of "Off"
B30 Bus Differential System

5.8.11 TELEPROTECTION INPUTS AND OUTPUTS

TELEPROT INPUTS
Range: Off, On, Latest/Off, Latest/On
Range: Off, On, Latest/Off, Latest/On
Range: Off, On, Latest/Off, Latest/On
Range: Off, On, Latest/Off, Latest/On
Range: Off, On, Latest/Off, Latest/On
Range: Off, On, Latest/Off, Latest/On