Checks during operation
Ignite the appliance as described in sec. 2.3.
Check that the fuel circuit and water systems are airtight.
Check the efficiency of the flue and air-fume ducts while the boiler is working.
Check that the water is circulating properly between the boiler and the systems.
Check the proper ignition of the boiler by performing various tests, turning it on and
off with the room thermostat or remote control.
Check that the burner door and fume chamber are tight.
Check that the burner works properly.
Analyse the combustion (with the boiler unit stable) and check that the content of
CO
in the fumes is between 11% and 12%.
2
Check the parameters are programmed correctly and perform any required custom-
ization (compensation curve, power, temperatures, etc.).
4.3 Maintenance
Periodical check
To ensure correct operation of the unit over time, have qualified personnel carry out a
yearly check, providing for the following:
The control and safety devices must function correctly.
The fume exhaust circuit must be perfectly efficient.
Check there are no obstructions or dents in the fuel supply and return pipes.
Clean the filter of the fuel suction line.
Measure the correct fuel consumption
Clean the combustion head in the fuel outlet zone, on the swirl disc.
Leave the burner running at full rate for approximately ten minutes, then analyse
the combustion, checking:
-
All the elements specified in this manual are set correctly
-
Temperatures of the fumes at the flue
-
CO2 percentage content
The air-fume end piece and ducts must be free of obstructions and leaks
The burner and exchanger must be clean and free of deposits. For possible clean-
ing do not use chemical products or wire brushes.
The gas and water systems must be airtight.
The water pressure in the cold water system must be approx. 1 bar; otherwise, bring
it to that value.
The circulating pump must not be blocked.
The expansion tank must be filled.
Check the magnesium anode and replace it if necessary.
The boiler casing, control panel and aesthetic parts can be cleaned with a soft
A
and damp cloth, if necessary soaked in soapy water. Do not use any abrasive
detergents and solvents.
Boiler cleaning
1.
Disconnect the power supply to the boiler.
2.
Remove the front top and bottom panel.
3.
Open the door by undoing the knobs.
4.
Clean the inside of the boiler and the entire path of exhaust fumes, using a tube
brush or compressed air.
5.
Then close the door, securing it with the knob.
To clean the burner, refer to the Manufacturer's instructions.
Burner disassembly
Remove the cover (B) by undoing the screw (A), thereby making all the accessories
accessible.
Undo the nut (C) and position the burner so as to access the nozzle.
fig. 35 - Burner disassembly
4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault,
the display will flash together with the fault symbol (detail 22 - fig. 1) indicating the fault
code.
There are faults that cause permanent shutdowns (marked with the letter "A"): to restore
operation press the RESET button (detail 8 - fig. 1) for 1 second or use the RESET on
the remote timer control (optional) if installed; if the boiler does not restart it is necessary
to eliminate the fault indicated in the operation LEDs.
Other faults cause temporary shutdowns (marked with the letter "F") which are automat-
ically reset as soon as the value returns within the boiler's normal working range.
Table. 8 - List of faults
Fault
Fault
code
A01
Burner block
Flame present signal
A02
with burner off
Overtemperature pro-
A03
tection activation
A04
Card parameter fault
Preheater fault (the
F07
contact does not close
in 120 seconds)
F09
Card parameter fault
F10
Delivery sensor 1 fault
F11
Card parameter fault
F12
Card parameter fault
F14
Delivery sensor 2 fault
F16
Card parameter fault
Supply voltage under
F34
170V.
F35
Faulty mains frequency Electric mains trouble
Incorrect system water
F37
pressure
F39
External probe fault
Incorrect system water
F40
pressure
A41
Sensor positioning
F42
Heating sensor fault
System water pressure
F47
sensor fault
cod. 3540S516 - Rev. 01 - 03/2015
Possible cause
Cure
Pump blocked
Replace
Faulty electric motor
Replace
Faulty oil valve
Replace
No fuel in tank, or water on bottom
Refill with fuel or suck the water
Oil line feed valves closed
Open
Dirty filters (line-pump-nozzle)
Clean
Pump unprimed
Prime and find the cause of unprim-
ing
Ignition electrodes dirty or not properly
Adjust or clean them
adjusted
Nozzle clogged, dirty or deformed
Replace
Unsuitable head and shutter adjustments Adjust
Faulty electrodes or earthed
Replace
Faulty ignition transformer
Replace
Faulty electrode wires or earthed
Replace
Electrode wires deformed by high temper-
Replace and protect
ature
Faulty valve or transformer electrical con-
Check
nections
Broken pump-motor joint
Replace
Pump inlet connected to return pipe
Correct the connection
Faulty photoresistance
Replace
Dirty photoresistance
Clean the photoresistance
Photoresistance short circuit
Replace the photoresistance
Extraneous light strikes the photoresist-
Eliminate light source
ance
Check the correct positioning and
Heating sensor damaged
operation of the heating sensor
No water circulation in the system
Check the circulating pump
Air in the system
Vent the system
Check the card parameter and mod-
Wrong card parameter setting
ify it if necessary
Preheater fault
Check the preheater
Wiring disconnected
Check the wiring
Check the card parameter and mod-
Wrong card parameter setting
ify it if necessary
Sensor damaged
Check the wiring or replace the sen-
Wiring shorted
sor
Wiring disconnected
Check the card parameter and mod-
Wrong card parameter setting
ify it if necessary
Check the card parameter and mod-
Wrong card parameter setting
ify it if necessary
Sensor damaged
Check the wiring or replace the sen-
Wiring shorted
sor
Wiring disconnected
Check the card parameter and mod-
Wrong card parameter setting
ify it if necessary
Electric mains trouble
Check the electrical system
Check the electrical system
Pressure too low
Fill the system
Sensor damaged
Check the sensor
Check the wiring or replace the sen-
Probe damaged or wiring shorted
sor
Probe disconnected after activating the
Reconnect the external probe or dis-
sliding temperature
able the sliding temperature
Check the system
Pressure too high
Check the safety valve
Check the expansion tank
Check the correct positioning and
Delivery sensor not inserted in boiler shell
operation of the heating sensor
Sensor damaged
Replace the sensor
Wiring disconnected
Check the wiring