HIM CopyCat Function

PowerFlex 750-Series drives and PowerFlex 7-Class drives provide a CopyCat function that enables you to upload
individual parameter sets for the host drive or any of its connected peripherals into the HIM. Furthermore, an Upload All
Ports function enables you to conveniently upload multiple parameter sets for the host drive and all of its connected
peripherals in one single file. In either case, this information can then be used as backup or can be transferred to another
drive or peripheral device by downloading the file from the HIM's memory.
The Upload All Ports and Download All Ports functions are only available for the host drive (Port 00) due to their unique
TIP
functionality.
Before beginning the Download All Ports function, verify that your option cards are located in the same ports as the drive you are
TIP
copying the parameters from. Also, verify the port you are working on before beginning the CopyCat from Device to HIM function.
The CopyCat function also enables you to rename or delete individual or multiple parameter sets stored in the HIM.
The HIM can store up to 50 individual parameter sets or up to 5 multiple parameter sets. Due to the memory capacity of
the HIM, these maximums will vary when storing combinations of individual and multiple parameter sets.
Generally, the upload or download transfer process manages all conflicts. However, the download will stop and a text
message will appear if any of the following conditions exist:
• A device mismatch, such as firmware revision, device type, or device series is detected.
• The drive is password protected.
• The drive is running.
You then have the option to completely stop the download or continue after noting the discrepancy for the parameters that
could not be downloaded. These parameters can then be manually adjusted.
When using the HIM with a PowerFlex 753 drive with firmware revision 1.05 or earlier, or a PowerFlex 755 drive with firmware
IMPORTANT
revision 1.10 or earlier, the CopyCat function cannot upload/download DeviceLogix values for DLX Out xx and DLX In xx parameters
and DeviceLogix program routines. Drives with a later firmware revision support this function, but the HIM does not support screen
formatting for the DeviceLogix program.
Creating CopyCat Files
1. Access the Status screen.
Stopped
0.000 Hz
Host Drive
240V
4.2A
20G...D014
00
ESC
REF
PAR#
2. Use the
or
Port 00 for the host drive).
3. Press the
key to display its last-viewed folder.
78
AUTO
F
TEXT
key to scroll to the Port of the device whose parameter set you want to copy (for example,
Rockwell Automation Publication 750-QS001A-EN-P - March 2015

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PowerFlex 753 and is the answer not in the manual?

Questions and answers

Adrian
March 24, 2025

Número de catálogo para powerflex 753

1 comments:
Mr. Anderson
March 24, 2025

The catalog number for the Allen-Bradley PowerFlex 753 is 20F11NC022JA0NNNNN.

This answer is automatically generated

Ray Fitz
April 17, 2025

How dO you change from Him pad to wire control?

This manual is also suitable for:

Powerflex 755

Table of Contents

Save PDF