About Test Procedures

After the installation is complete, you should perform the following tests:

System Test:

Dialer Test:
Go/No Go Test:
RF Sniffer Mode:
Battery Tests:
System Test
With the system in the disarmed state, check that all zones are intact (not faulted). Doors and
windows with contacts should be closed, PIRs should be covered (use a cloth to mask them
temporarily if necessary). If a "NOT READY" message is displayed, press [∗] to display the faulted
zone(s). Restore faulted zone(s) if necessary, so that the "READY" message is displayed.
1. Enter Installer Code + 5 [ TEST ] , then press "0" at the prompt to start Walk Test mode.
1=DIAL, 0=WALK
The following will be displayed:
TEST IN PROGRESS
A Contact ID report will also be sent (code 607)
2. Upon entering the system test mode, the outside sounder should sound for 1 second.
If the backup battery is discharged or missing, the sounder may not turn on and a "LOW
BATTERY" report will be transmitted with a "TEST" report.
The touchpad will beep once per minute as a reminder that the system is in the Test mode.
NOTE: Wireless motion detectors (Passive Infrared units) will send signals out only if they have
been inactive for 3 minutes (conserves battery life).
3. Test all sensors using the procedure described in the User's Guide "Testing the System" section.
4. After checking sensors, turn off the test mode by entering installer code + OFF.
NOTE: Test mode automatically ends after 4 hours.
Checks that all zones have been installed properly and the system properly
responds to faults.
Checks that the phone connection to the central station is working properly.
Checks that transmissions can be received from transmitters. Should be
performed before permanently mounting transmitters.
Checks that RF transmitter serial numbers have been properly entered into the
system.
Automatic battery tests are performed by the system. See Automatic Battery Test
paragraph for details.
("dd" displayed on English Display Touchpads)
S E C T I O N

Testing the System

1 3
13-1

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Safewatch Pro 3000 and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Security manager 3000

Table of Contents

Save PDF