RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
Table Of Contents • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Conventions Used in This Manual............................v Features and Installation Highlights............................
Page 4
Table Of Contents (continued) Zone Programming ................................5-1 About Zone Programming..............................5-1 56 Zone Programming Procedure............................ 5-1 Completing Zone Programming ............................5-4 ∗58 Expert Programming Mode Procedures ........................5-4 To Enter and Duplicate Wireless Keys ..........................5-6 Output Device Programming..............................6-1 About Output Device Programming...........................
Conventions Used in This Manual • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Before you begin using this manual, it is important that you understand the meaning of the following symbols (icons).
Safewatch Pro Installation and Setup Guide Compatible Devices • Supports up to 8 Addressable Touchpads: English Display Touchpad, Custom English Display Touchpad • Supports up to five (5) 4219, 4229 addressable zone expander modules for up to 40 expansion zones •...
S E C T I O N Mounting and Wiring the Control • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This section describes the procedures for mounting and wiring this control and its peripheral devices.
Safewatch Pro 3000 Installation Instructions Notes Mounting Board with RF Receiver • Do not mount the cabinet on or near metal a. Remove the receiver board from its case, then objects. This will decrease RF range and/or block insert the top of the board into the slots at the top RF transmissions from wireless transmitters.
Mounting and Wiring the Control Notes Wiring to Touchpads • Typical English Display: 6137B Connect touchpads to the control’s touchpad • Typical Custom English Display: 6139B terminals as shown on the Summary of Connections • The system supports up to 8 touchpads, which diagram.
Safewatch Pro 3000 Installation Instructions Sounder (Bell) Connections Notes This control complies with NFPA requirements for 1. Make sounder connections to alarm output terminals temporal pulse sounding of fire notification appliances. 3 (+) and 4 (–). Temporal pulse sounding for a fire alarm consists of: For supervised output, continue with steps 2 and 3.
Mounting and Wiring the Control Notes Backup Battery • Refer to the California State Fire Marshal and 1. Place the 12-volt backup battery in the cabinet. UL Residential Fire requirements statement 2. After all connections to the control are completed, below, if applicable.
Safewatch Pro 3000 Installation Instructions Notes Hardwire Zones • EOLR: If the EOLR is not at the end of the loop, Normally Open Zones the zone will not be properly supervised, and the 1. Connect open circuit devices in parallel across the...
Mounting and Wiring the Control Notes 4219/4229 Expansion Zones • The system supports up to 40 expansion zones 1. Connect each module to the control’s touchpad (NO or NC) using up to five (5) 4219 and/or 4229 terminals. Zone Expander Modules. 2.
Safewatch Pro 3000 Installation Instructions Installing the RF Receiver Notes • You must use one of the following receivers: 1. Set Device Address to “00” as described in its RF Receiver No. of Zones instructions (set all switches to the right, “off”...
Mounting and Wiring the Control Transmitter Battery Life • Batteries in the wireless transmitters may last from 4 to 7 years, depending on the environment, usage, and the specific wireless device being used. Factors such as humidity, extreme temperatures, as well as large temperature variations may all reduce the actual battery life in a given installation.
Safewatch Pro 3000 Installation Instructions Notes Connecting Relay Modules • Use 4204 or 4229 modules. 1. Mount either remotely or in the control panel. 2. Connect to control’s touchpad terminals using the • Supervision: 4204 and 4229 modules are connector harness supplied with the module. Use supervised against removal.
Mounting and Wiring the Control Notes Powerline Carrier Devices • When using Powerline Carrier devices, you must 1. Install the powerline carrier devices according to the use a 4300 or 1321X10 Transformer instead of instructions included with each. the 1321 Transformer. 2.
Safewatch Pro 3000 Installation Instructions Notes Phone Line/Phone Module Connections • Use 4285 or 4286 Phone Modules. 1. Connect incoming phone line and handset wiring to Compatibility: 4286 Phone Modules must have the main terminal block (via an RJ31X jack) as software version WA4286-15.1 or higher (refer to...
Mounting and Wiring the Control Notes Long Range Radio Connections • Use compatible Long Range Radios (e.g., Connect the data in/data out terminals and voltage 7720PLUS, 7820, 7835C, or 7845C). input terminals of the Long Range Radio to the control's touchpad connection points. Set the radio’s address to “03”...
Program basic data fields used for setting the various system options. Most of the data fields in this system have been programmed for specific ADT values. However, some fields must be programmed for each particular installation to establish its specific alarm and reporting features.
Safewatch Pro 3000 Installation Instructions Touchpads Touchpads are identified by predefined addresses as follows: Address Touchpad Program Field • always enabled for partition 1, all sounds enabled. touchpad 1* • data field *190 touchpad 2 • data field *191 touchpad 3 •...
Function Keys To assign functions to the function keys, use *57 Function Key menu mode. To assign emergency key functions (function key option “00”), first program the respective emergency zone number (95 for “A” key, 96 for “C” key, 99 for “B” key) with the desired zone type using *56 Zone Programming mode, then use *57 Function Key menu mode to assign the desired key.
Page 26
Safewatch Pro 3000 Installation Instructions • Usually assigned to a zone containing an emergency button. Type 06 • Sends a report to the central station but provides no touchpad display or 24-hour Silent Alarm sounding. • Assign to a zone that has an emergency button.
• Usually assigned to all sensors or contacts on exterior doors and windows where Type 24 Silent Burglary bells and/or sirens are NOT desired. • Provides an instant alarm, with NO audible indication at any touchpad or external sounder, if the zone is faulted when the system is armed in the Away, Stay, or Instant, modes.
Page 28
Loading Factory Defaults/Initializing for Download Press ∗97 while in Program Mode. This resets all data fields to the ADT To Load Default Entries default values shown in the boxes in the Program Form. Use ∗ 97 only if you wish to return to the original factory-programmed defaults.
S E C T I O N Data Field Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Data Field Programming The following pages list this control’s data fields in numerical order.
Safewatch Pro 3000 Installation Instructions FIELD TITLE and DATA ENTRIES EXPLANATION If selected, all messages programmed to go to the primary telephone Long Range Radio Output line receiver will also be sent to the connected 7720PLUS, 7820, 0 = not used 7835, or 7845 Radio (sent in Contact ID format).
Dialer Programming ( ∗ 40 – ∗ 50) FIELD TITLE and DATA ENTRIES EXPLANATION To clear entries from field, press ∗40∗. If fewer than 6 digits need to PABX Access Code be entered, exit by pressing [∗], which advances to the next field. Enter up to 6 digits if PABX is needed to access an outside line.
Safewatch Pro 3000 Installation Instructions FIELD TITLE and DATA ENTRIES EXPLANATION Dynamic Signaling Delay Intended for use with Long Range Radio reporting. This field lets you select the time the panel should wait for 0 = disabled (both signals sent) acknowledgment from the first reporting destination (see ∗55) before...
FIELD TITLE and DATA ENTRIES EXPLANATION Trouble Report Code This will be sent if a zone has a trouble condition. 0 = no report 1st digit non-zero = send report Bypass Report Code This will be sent when a zone is manually bypassed. 0 = no report 1st digit non-zero = send report Timing of this report is random with up to a 4-hour delay.
Safewatch Pro 3000 Installation Instructions Miscellaneous System Fields FIELD TITLE and DATA ENTRIES EXPLANATION Enter the start and end month for daylight savings time, if applicable Daylight Saving Time to the region. Start/End Month 0 = Disabled # + 10 = Oct...
Page 35
FIELD TITLE and DATA ENTRIES EXPLANATION Select the desired options by adding the values of each desired option. Option Selection Multiple choice example: for both AAV and Exit delay restart†, enter 0 = none # + 12 (4 + 8); for all (1 + 4 + 8), enter # + 13. 1 = Bell Supervision†...
Safewatch Pro 3000 Installation Instructions Pager Programming Fields FIELD TITLE and DATA ENTRIES EXPLANATION Pager #1 Phone No. If you enter fewer than 20 digits, exit by pressing [∗] and next field *160 number. To clear entries from this field, press ∗160∗.
FIELD TITLE and DATA ENTRIES EXPLANATION Pager 3 Phone No. If you enter fewer than 20 digits, exit by pressing [∗] and next field *166 number. To clear entries from this field, press ∗166∗. Enter up to 20 digits See field ∗161 for explanation of entries. If fewer than 16 characters, Pager 3 Characters *167 exit by pressing [∗] and next field number.
Safewatch Pro 3000 Installation Instructions Configurable Zone Type Programming Fields The system allows you to define up to four custom zone types, based on the options described below, which can be assigned to zones that require customized responses. All of these zone types can be programmed via the downloader.
Page 39
Configurable Zone Type Charts DIGIT 1 DIGIT 2 Response when system disarmed and zone is: Auto Restore Vent Zone Intact EOL Open Shorted RF zone normal RF zone N/A RF zn off-normal INTACT OPEN SHORTED 0 = normal 0 = normal 0 = normal 0 = no 0 = no...
Safewatch Pro 3000 Installation Instructions Touchpad Programming Fields FIELD TITLE and DATA ENTRIES EXPLANATION Touchpad 2 Touchpad Device Address 17 *190 First digit: Enter the partition in which the touchpad is located. 1st Digit – Partition Assignment: Second digit: Enter the desired sound option for this touchpad.
S E C T I O N Zone Programming ( 56 and 58 Menu Modes) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Zone Programming 56 Zone Programming is used to program zones, zone types, report codes, enroll 5800 RF Wireless Transmitter serial numbers, and identify the type of loop input device(s).
Page 42
Safewatch Pro 3000 Installation Instructions PROMPT VALID ENTRIES EXPLANATION Zone Type (ZT) Each zone must be assigned to a zone type, which defines the way in 10 Zone Type which the system responds to faults in that zone. 00-25, 77, 90, 91 = zone type...
Page 43
PROMPT VALID ENTRIES EXPLANATION Used only when enrolling wireless transmitters. Serial number Entry and 10 INPUT S/N: a. Transmit two open/close sequences. If using a button-type Loop Number Entry A 0 2 2 - 4 0 6 4 transmitter, press and release the button twice, but wait about 4 see explanation seconds before pressing the button the second time.
(zone number, zone type, loop number, etc.) relevant to that device. ∗58 Expert Programming Mode Procedures This method is designed for use by installers with previous experience in programming ADT control panels. This mode is also used to program wireless keys using pre-defined templates.
Page 45
PROMPT VALID ENTRIES EXPLANATION Manually enter the serial number (found on the transmitter label), Serial number 10 INPUT S/N: by typing digits in the “X” locations, using the [A] (advance) or [B] S/N = serial number A X X X - X X X –...
Safewatch Pro 3000 Installation Instructions To Enter and Duplicate Wireless Keys This procedure programs the wireless keys, but a key is not active until it is assigned to a user number (see System Operation section, assigning attributes command). If the D key was previously pressed (from *58 Menu mode) to enter and duplicate 5804 and/or 5804BD wireless keys, the following screens appear.
Page 47
Not Confirmed If the serial number transmitted does not match the serial number Entd A022-4063 [ ∗ ] to continue entered, a display similar to the one shown will appear. If the loop Rcvd A022-4064 number does not match, it will also be displayed. If so, activate the button on the wireless key once again.
Page 48
Safewatch Pro 3000 Installation Instructions...
S E C T I O N Output Device Programming (*79/ * 80 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Output Device Programming Output Devices: The system supports up to 16 relays and/or Powerline Carrier devices (X-10...
Page 50
Safewatch Pro 3000 Installation Instructions Start Output Device Mapping by pressing *79 while in Data Programming Mode. The following prompts are displayed: ∗79 Menu Mode PROMPT VALID ENTRIES EXPLANATION Device Output Number This is the logical (or reference) relay number as used in the system.
*80 Menu Mode: Defining Output Functions Use this mode to program up to 48 output definitions that provide automated control of any of the 18 output devices, based on events ocurring on individual zones or zones with certain zone types. Each output definition is identified by an output function number, and includes the following components: Output Definition Components Component...
Page 52
Safewatch Pro 3000 Installation Instructions Activated By Select where the initiating event for this output definition is to occur 01 Activated By: as follows: 0 = delete Zone List 0 = delete (deletes the data set number and any previous...
Page 53
“C” If zone number was selected, this screen appears. Zone Number 01 Enter Zn No. Enter the desired zone number associated with this output number. Press [ ] to continue. Enter the zone event that will activate this output. 01 Enter Event 0 = restore;...
Page 54
Safewatch Pro 3000 Installation Instructions...
S E C T I O N Zone Lists (∗ ∗ 81 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Zone Lists Zone lists let you group individual zones for use with certain system actions.
Page 56
Safewatch Pro 3000 Installation Instructions Notes: • Any list may include any or all of the system's zone numbers. • A zone list can be assigned to more than one output relay. • When creating zone list 4 for cross zoning, include only zones assigned to zone types 3, 4, or 5. Do not include zones that have delays (entry/exit zones, interior w/delay) or 24-hour zones, as these zone types may produce unpredictable operation and may not function as intended.
S E C T I O N Function Key Programming ( 57 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Function Key Programming The system provides the ability to program each of the four keypad function keys to perform one of 12 system operations.
Page 58
Safewatch Pro 3000 Installation Instructions...
S E C T I O N Alpha Descriptor Programming (*82 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Descriptor Programming The system lets you assign zone descriptors for protection zones, touchpad panics, and RF receiver supervision faults.
Page 60
Safewatch Pro 3000 Installation Instructions Flashing Cursor To delete or change the default descriptor for zone 1, press [ ] plus Z N 0 1 the same zone number (01). This will clear that descriptor and allow changes to be made at the flashing cursor.
Adding Custom Words (will not be annunciated by 4285/4286 Phone Module) You can add up to 10 installer-defined words to the built-in vocabulary, which can then be used when programming zone descriptors. Each of the 10 words can actually consist of a word string of one or more words, but no more than ten characters can be used for each word or word string.
Page 62
ALPHA VOCABULARY LIST (For Entering Zone Descriptors) (Word Space) BOTTOM CELLAR DESK • 012 BABY BREAK • 037 CENTRAL • 052 DETECTOR • 013 BACK • 026 BUILDING CIRCUIT • 053 DINING • 001 DISCRIMINATOR • 014 • 040 CLOSED •...
S E C T I O N Creating Schedules • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Schedules The system provides up to 32 schedules, which can be used to control up to 12 types of system events at pre-defined times.
Page 64
Safewatch Pro 3000 Installation Instructions Stop Time Enter the event’s stop time and days of the week to occur. S T A R T S M T W T F S To select days, position the cursor under the desired days using the...
S E C T I O N System Operation • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Security Codes The system supports up to 48 security codes, which can each be assigned one of 5 authority levels.
Safewatch Pro 3000 Installation Instructions Touchpad Functions The following is a brief list of system commands. For detailed information concerning system functions, refer to the User's Manual. Function Description Silence alarms Pressing any key will silence the touchpad sounder for 10 seconds. Disarming the system will silence both touchpad and external sounders.
Panic Keys There are three Panic keys (A, B, and C) that, if programmed, can be used to manually initiate alarms and send a report to the central station. Each key can be programmed for 24-hour Silent, 24-hour Audible, Fire, or Personal Emergency responses.
Page 70
Safewatch Pro 3000 Installation Instructions Alpha Display Fixed Disp. Meaning Modem Comm The system is in communication with the central station for change of function or status verification. no display no display Power Failure If there is no touchpad display at all and the LEDs are unlit, operating power (AC and battery) for the system has stopped and the system is inoperative.
S E C T I O N Testing the System • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Test Procedures After the installation is complete, you should perform the following tests: System Test:...
Safewatch Pro 3000 Installation Instructions Checking Transmitter Enrollment (Sniffer Mode) Use this mode to verify that all transmitters have been properly programmed. Make sure both partitions are disarmed before trying to enter this mode, since this is a system-wide command.
Dialer Communication Test 1. Enter Installer Code + 5 [ TEST ], then press “1” at the prompt to start the Dialer Test. 1=DIAL, 0=WALK The following will be displayed (accompanied by 2 beeps) if test is successful: PHONE OKAY (“Cd”...
Page 74
Safewatch Pro 3000 Installation Instructions 13-4...
5800 Series Transmitter Input Loop Identification • All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5804's four inputs require four programming zones). •...
Page 78
Safewatch Pro 3000 Installation Instructions Compatible 5800 Series Transmitters Table Also refer to Appendix A for transmitter input loops/button locations. Model Product Enter as Description Input Device Type • 5801 Wireless UR or RF Has four pushbuttons, each with a unique input (loop) Panic code.
Page 79
Model Product Enter as Description Input Device Type • 5819 Shock Connects to externally mounted inertia-type shock detector (not supplied). Processor Transmitter • Has built-in tampered cover switch. • Has 3 unique input (loop) codes: Loop 1: Terminals for a wired, N.C. sensor loop. Loop 2: For a closed circuit contact loop using the built-in reed switch in conjunction with a magnet.
S E C T I O N Regulatory Agency Statements • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • RADIO FREQUENCY EMISSIONS Federal Communications Commission (FCC) Part 15 This device complies with part 15 of the FCC rules.
Page 82
Safewatch Pro 3000 Installation Instructions UL NOTICES 1. The 4285/4286 Phone module and 7720PLUS or 7820 Long Range Radios have not been UL tested and cannot, therefore, be used in a UL installation. 2. Entry Delay No. 1 (field 35) cannot be greater than 20 seconds, and Entry Delay No.
S E C T I O N Limitations and Warranty • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against...
Page 84
Safewatch Pro 3000 Installation Instructions WARNING THE LIMITATIONS OF THIS ALARM SYSTEM (Continued) The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working properly.
Page 85
ADEMCO Limited Warranty Alarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions, subsidiaries and affiliates ("Seller"), 165 Eileen Way, Syosset, New York 11791, warrants its products to be in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for 24 months from the date stamp control on the product or, for products not having an ADEMCO date stamp, for 12 months from date of original purchase unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply.
THAT MAY CAUSE UNDESIRED OPERATION. PROGRAMMING MUST BE DONE WITH A WEEKLY TESTING IS REQUIRED TO ENSURE 6139B BUT NEED NOT SAFEWATCH PRO 3000 PROPER OPERATION OF THIS SYSTEM. REMAIN IN THE SYSTEM (SET TO ADDRESS 16). SECURITY MANAGER 3000 ASSEMBLED IN MEXICO File No.
Need help?
Do you have a question about the Safewatch Pro 3000 and is the answer not in the manual?
Questions and answers