Mains cable fuses

Fuses for short-circuit protection of the mains cable are listed below. The fuses also
protect the adjoining equipment of the drive in case of a short-circuit. Check that the
operating time of the fuse is below 0.5 seconds. The operating time depends on
the supply network impedance and the cross-sectional area, material and length of
the supply cable. See also Planning the electrical installation:
short-circuit
Note 1: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 2: Larger fuses must not be used.
Note 3: Fuses from other manufacturers can be used if they meet the ratings.

Standard gG fuses

ACS800-02
size
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0080-2
-0100-2
-0120-2
-0140-2
-0170-2
-0210-2
-0230-2
-0260-2
-0300-2
Three-phase supply voltage 380 V, 400 V or 415 V
-0140-3
-0170-3
-0210-3
-0260-3
-0320-3
-0400-3
-0440-3
-0490-3
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0170-5
-0210-5
-0260-5
-0320-5
-0400-5
-0440-5
-0490-5
-0550-5
-0610-5
Technical data
protection. For UL recognized fuses, see
Input
current
A
A
201
250
550 000
239
315
1 100 000
285
315
1 100 000
391
500
2 900 000
428
500
2 900 000
506
630
4 000 000
599
630
4 000 000
677
800
7 400 000
707
800
7 400 000
196
250
550 000
237
315
1 100 000
286
315
1 100 000
438
500
2 900 000
501
630
4 000 000
581
630
4 000 000
674
800
7 400 000
705
800
7 400 000
191
250
550 000
243
315
1 100 000
291
315
1 100 000
424
500
2 900 000
498
630
4 000 000
543
630
4 000 000
590
630
4 000 000
669
800
7 400 000
702
800
7 400 000
Fuse
2
A
s
V
Manufacturer
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
Thermal overload and
US
tables.
Type
OFAF1H250
OFAF2H315
OFAF2H315
OFAF3H500
OFAF3H500
OFAF3H630
OFAF3H630
OFAF3H800
OFAF3H800
OFAF1H250
OFAF2H315
OFAF2H315
OFAF3H500
OFAF3H630
OFAF3H630
OFAF3H800
OFAF3H800
OFAF1H250
OFAF2H315
OFAF2H315
OFAF3H500
OFAF3H630
OFAF3H630
OFAF3H630
OFAF3H800
OFAF3H800
PDM code: 00096931-G
IEC size
1
2
2
3
3
3
3
3
3
1
2
2
3
3
3
3
3
1
2
2
3
3
3
3
3
3