P h enomena
If the unit cannot be operated properly after test run, refer to the following table to find the cause.
Wired remote controller
PLEASE WAIT
PLEASE WAIT
Check code
Display messages do not
appear even when operation
switch is turned ON (operation
lamp does not light up).
N ote: O p eration is not p ossib le for ab out 30 sec onds after c anc ellation of func tion selec tion. ( C orrec t op eration)
For description of each LED (LED1, 2, 3) provided on the FTC, refer to the following table.
LED1 (power for microprocessor)
LED2 (power for remote controller)
LED3 (communication between FTC and outdoor units)
OCH526C
Symptom
LED 1, 2 (PCB in outdoor unit)
For about 2
After LED 1, 2 are lighted, LED 2 is
minutes after
turned off, then only LED 1 is
power-on
lighted. (Correct operation)
Only LED 1 is lighted.
Subseq uent to
about 2 minutes
after power-on
Only LED 1 is lighted.
Indicates whether control power is supplied. Make sure that this LED is always lit.
Indicates whether power is supplied to the remote controller.
This LED lights only in the case of the FTC which is connected to the outdoor unit
refrigerant addresses "0".
Indicates state of communication between the FTC and outdoor units.
Make sure that this LED is always blinking.
C ountermeasure
WEEKLY
For about 2 minutes following power-on,op-
eration of the remote controller is not possible
due to system start-up. (Correct operation)
Connector for the outdoor unit ' s protection
device is not connected.
Reverse or open phase wiring for the outdoor
LED 1, 2 blink.
unit' s power terminal block (L1, L2, L3)
Incorrect wiring between FTC and outdoor
(incorrect polarity of S1, S2, S3)
LED 1 blinks twice,
LED 2 blinks once.
Remote controller wire short
SIMPLE
AUTO OFF
Cause