Functions Of The Major Components Of Outdoor Unit - Mitsubishi Electric PUHY-P200 Service Handbook

Hide thumbs Also See for PUHY-P200:
Table of Contents

Advertisement

[3-3 Functions of the Major Components of Outdoor Unit ]

3-3

Functions of the Major Components of Outdoor Unit

Part
Symbols
name
(functions)
Com-
MC1
pressor
(Comp1)
High
63HS1
pres-
sure
sensor
Low
63LS
pres-
sure
sensor
Pres-
63H1
sure
switch
HWE14040
Notes
Usage
Adjusts the amount of circulating
refrigerant by adjusting the operat-
ing frequency based on the oper-
ating pressure data
1) Detects high pressure
2) Regulates frequency and pro-
vides high-pressure protec-
tion
1) Detects low pressure
2) Provides low-pressure pro-
tection
3) Defrost control during heating
operation
1) Detects high pressure
2) Provides high-pressure pro-
tection
Specifications
P200, P250 models
Low-pressure shell scroll
compressor
wirewound resistance
20°C [68°F] : 0.72 Ω
P300, P350 models
Low-pressure shell scroll
compressor
wirewound resistance
20°C [68°F] : 0.32 Ω
P400 model
Low-pressure shell scroll
compressor
wirewound resistance
20°C [68°F] : 0.30 Ω
P450, P500 models
Low-pressure shell scroll
compressor
wirewound resistance
20°C [68°F] : 0.43 Ω
Pressure
63HS1
0~4.15 MPa [601psi]
Vout 0.5~3.5V
1 2 3
0.071V/0.098 MPa [14psi]
Pressure [MPa]
Con-
=1.38 x Vout [V]-0.69
nector
Pressure [psi]
=(1.38 x Vout [V] - 0.69) x 145
1
GND (Black)
2
Vout (White)
3
Vcc (DC5V) (Red)
Pressure
63LS
0~1.7 MPa [247psi]
Vout 0.5~3.5V
1 2 3
0.173V/0.098 MPa [14psi]
Pressure [MPa]
Con-
=0.566 x Vout [V] - 0.283
nector
Pressure [psi]
=(0.566 x Vout [V] - 0.283) x 145
1
GND (Black)
2
Vout (White)
3
Vcc (DC5V) (Red)
4.15MPa[601psi] OFF setting
- 61 -
Check method
GB

Advertisement

Table of Contents
loading

Table of Contents