1 Important information Serial number Safety information The serial number for F2040 can be found on the side This manual describes installation and service proced- of the foot. ures for implementation by specialists. F2040-8 This appliance can be used by children...
F2040-16 Serial number Caution Always give the product's serial number when reporting a fault. Country specific information Installer manual This installer manual must be left with the customer. NIBE™ F2040 Chapter 1 | Important information...
✔ Description Notes Signature Date System flushed System vented Particle filter Shut-off and drain valve Charge flow set Fuses property Safety breaker Communication cable connected F2040 addressed (only when cascade connection) Miscellaneous Chapter 1 | Important information NIBE™ F2040...
(see page 7). Care must be exercised so that the heat pump is not scratched during installation. Do not place F2040 directly on the lawn or other non solid surface. Chapter 2 | Delivery and handling...
Page 9
The section of the pipe that can be affected by frost must be heated by the heating cable to prevent freezing. Route the pipe downward from F2040. The outlet of the condensation water pipe must be at a depth that is frost free or alternatively indoors (with reservation for local ordinances and regula- tions).
Installation area The distance between F2040 and the house wall must be at least 150 mm. Clearance in front of F2040 should be at least one metre. Chapter 2 | Delivery and handling...
Page 17
List of components F2040-8, -12, -16 Cable, incoming supply Pipe connections QM35 Service valve, liquid side QM36 Service valve, gas side Connection, heating medium out of F2040, G3/4" (Ø22 mm) Connection, heating medium in to F2040, G3/4" (Ø22 mm) Sensors etc.
Pipe installation must be carried out in accordance with current norms and directives. -8, -12 F2040 can only operate up to a return temperature of about 55 °C and an outgoing temperature of about 58 °C from the heat pump.
F2040-16 Docking alternatives F2040 can be installed in several different ways. The requisite safety equipment must be installed in accord- ance with current regulations for all docked options. See www.nibe.eu for more docking options. Connecting accessories Instructions for connecting accessories are in the install- ation instructions provided for the respective accessory.
If a miniature circuit breaker is used this should have motor characteristic "C" (compressor operation). For MCB size see "Technical Specifications". AA23 F2040 does not include a circuit breaker on the in- coming power supply. The heat pump’s supply cable AA23-S2 (W1) must be connected to a circuit-breaker with at least a 3 mm breaking gap.
To prevent interference, unscreened commu- nication and/or sensor to external connections cables must not be laid closer than 20 cm to high voltage cables when cable routing. Power connection F2040-8 Power connection Incoming supply Chapter 5 | Electrical connections NIBE™ F2040...
(EB14) is connected via cable grommet UB3, see Extern- al heating cable KVR 10 (Accessory) on page 28. List of components Cable grommet, cascade connection Cable grommet, communication Cable grommet, heating cable (EB14) Cable, incoming supply Chapter 5 | Electrical connections NIBE™ F2040...
Page 29
F2040-8 F2040-16 Cables for communication (W2) are routed through ferrite beads/EMI filters. Secure the communication cable (W2) here using two cable ties. F2040-12 Secure the communication cable (W2) here using two cable ties. NIBE™ F2040 Chapter 5 | Electrical connections...
Page 30
External heating cable KVR 10 (Accessory) Cable routing The following images show recommended cable rout- F2040 is equipped with a plinth for external heating ing from the distribution box to the condensation water cable EB14 not supplied). The connection is fused with pipe.
Heating cable (EB14) On the communication card (AA23-S2) the communic- F2040-16 ation address is selected for F2040 to NIBE control module. Default has F2040 address 1. In a cascade connection all F2040 must have a unique address. The address is coded in binary.
2. Vent the system using the venting nipple (QM20) on the enclosed flexible hose and possibly the cir- culation pump. Compressor heater F2040 is equipped with a compressor heater that heats the compressor before start-up and when the com- pressor is cold. NOTE The compressor heater must have been con- nected for 6 –...
This is done by switching on the control voltage and disconnecting AA23-S2 the communication cable. 2. F2040 must be addressed if it is to have another AA23-X4 address than 1. See chapter Addressing via cascade connection, on page 29.
When the system is stable (correct pressure and all air elimin- ated) the automatic heating control system can be set as required. Chapter 6 | Commissioning and adjusting NIBE™ F2040...
Instructions for adjusting hot water charging are in the installation manual for the respective indoor section. See page 38 for the list of the indoor sections and ac- cessories that can be used with F2040. NIBE™ F2040 Chapter 6 |...
Check any external switches. NOTE Incorrect settings in NIBE SMO or NIBE indoor As F2040 can be connected to a large number module of external units, these should also be checked. See the manual for the indoor module. F2040 is not operational NOTE F2040 communicates all alarms to the indoor module.
Connection to card (PWB1) Sensor placement F2040-8 EB10 EB11 63H1 FM01 PWB1 NIBE™ F2040 Chapter 7 | Disturbances in comfort...
Page 38
EB10 FM01 Tho-R2 BT16 BT14 BT17 BT28 Tho-R1 Tho-D Tho-S Tho-A Sensor placement in F2040 Sensors etc. BE1 (CT) Current sensor Defrost/Cooling BP1 (63H1) High pressure pressostat BP2 (LPT) Low pressure transmitter Pressure sensor, condenser Temperature sensor, heating medium re-...
Page 39
Data for sensor in F2040 Data for return line temperature sensor (BT3), con- densor supply (BT12) and fluid pipe (BT15) Tho-D Temperature Resistance Voltage (VDC) (kΩ) (°C) (kOhm) 351.0 3.256 251.6 3.240 182.5 3.218 133.8 3.189 99.22 3.150 74.32 3.105 56.20...
Part no. 069 112 Condensation water pipe,different VVM 500 lengths. Part no. 069 400 Earth circuit breaker 1-phase. SMO 20 KVR 10-10 F2040 Control module 1 metre Part no. 067 224 Part no. 067 233 RSK no. 625 10 06 KVR 10-30 F2040 SMO 40 2.5 metres...
Page 41
Copper Part no. 083 231 VPB 1000 Hot water heater with charge coil Copper Part no. 083 240 VPAS 300/450 Water heater with double-jacketed vessel and solar coil. Copper Part no. 087 720 Enamel Part no. 087 710 NIBE™ F2040 Chapter 8 | Accessories...
9 Technical data Dimensions and setting-out coordinates F2040-8 F2040 Adjustable 40-50 1035 Ø40* * Accessory KVR 10 is required. F2040-12 Adjustable 40-50 1075 1145 Ø40* * Accessory KVR 10 is required. Chapter 9 | Technical data NIBE™ F2040...
Page 43
* Accessory KVR 10 is required. Free space behind Fritt utrymme bakom 600 mm Minimum free Free space in Minimum free Min. distance when using Min. avstånd space front space several F2040 vid användning av flera F2040 NIBE™ F2040 Chapter 9 | Technical data...
The sound pressure levels are further affected by walls, bricks, differences in ground level, etc and should F2040 is usually placed next to a house wall, which therefore only be seen as guide values. gives a directed sound distribution that should be F2040 adjusts the fan speed depending on the ambient considered.
-20/43 Defrosting system reverse cycle Heating medium Min/Max system pressure heating medium 0.05/0.25 (0.5/2.5bar) Min volume, climate system, heating/cooling Min volume, climate system, under floor cooling Max flow, climate system 0.38 0.57 0.79 NIBE™ F2040 Chapter 9 | Technical data...
Page 46
If the impedance in the mains connection point is higher than that stated check with the power supplier before purchasing the equipment. Specified output is limited with lower fusing. Chapter 9 | Technical data NIBE™ F2040...
Page 47
Working range, compressor operation - heating F2040-8, -12. -16 Water temperature °C Supply temperature Return temp Outdoor air temperature °C During shorter time it is allowed to have lower working temperatures on the water side, e.g. during start up. Working range, compressor operation - cooling...
Page 50
F2040-12 Chapter 9 | Technical data NIBE™ F2040...
Page 51
(BK) (WH) ° t ° t ° t ° t ° t ° t EB11 EB10 BP2 LPT BT16 BT14 BT17 BT28 Tho-P Tho-R2 Two fan unit only 63H1 Tho-R1 Tho-D Tho-S Tho-A NIBE™ F2040 Chapter 9 | Technical data...
Page 52
F2040-16 Chapter 9 | Technical data NIBE™ F2040...
List of components, 11 External heating cable (KVR 10), 28 Transport and storage, 6 Troubleshooting, 34 Sensor placement, 35 Filling and venting the heating medium system, 30 Important information, 2 Safety information, 2 Chapter 10 | Item register NIBE™ F2040...
Page 56
NIBE AB Sweden Hannabadsvägen 5 Box 14 SE-285 21 Markaryd info@nibe.se www.nibe.eu 231844...
Need help?
Do you have a question about the F2040 and is the answer not in the manual?
Questions and answers