Lenovo System x PDU Technical Reference page 165

Table of Contents

Advertisement

.
40K9611 – DPI 32A Cord (IEC 309 3P+N+G)
IEC-309 3P+N+G (4.3m) 32A, 3P5W plug (Type 532P6W)
32A (32A / Phase) 380-415VAC Three Phase Wye
96A Total Circuit Capacity
Only a receptacle or a connector is needed to mate with the plug on the PDU input
line cord. See the
Additional Plug Information
further details on IEC309.
Matching receptacle listing 532R6W IP-67 HUBBELL, Hubbell receptacle P/N
HBL532R6W
Matching connector listing 532C6W IP-67 HUBBELL, Hubbell connector P/N
HBL532C6W
Used with:
Basic PDUs:
39Y8941 –
DPI® Enterprise – C13 PDU
39Y8948 –
DPI Enterprise – C19 PDU
71762NX –
Ultra Density Enterprise PDU
Monitored PDU:
39M2816
–DPI Enterprise PDU+ C13
71762MX – DPI Ultra Density Enterprise PDU+ (withdrawn)
Switched and Monitored PDUs:
46M4002 –
1U 9 C19 / 3 C13 Switched and Monitored PDU
46M4004 –
1U 12 C13 Switched and Monitored PDU
Figure 102: IEC 309 3P+N+G 32A plug
* Note: For Australia and New Zealand refer to the
section.
165
on page
191
in this document for
'Re-termination for
A/NZ'