Specifications - Lenovo System x PDU Technical Reference

Table of Contents

Advertisement

.

Specifications

The following table are specifications for the 46M4004 C13 Switched and Monitored
PDU.
Specifications Line cord PN Line cord PN Line cord PN Line cord PN Line cord PN
Input Line
40K9611
Cord Type*
Type
32A/380-
415V
Outlets types
twelve IEC
C13
Power
22080VA @
Capacity**
230V
Power Limit
10A
per Outlet
Grouping
Two C13
outlets per
breaker
Four C13
outlets per
phase
Power Limit
20A per
per Group
breaker
32A per
phase
Power Limit
96A
per PDU
Monitoring/
No/No
Switching
U Space
1U or side pocket
Grounding
Yes on back panel
Screw
* For input line cord part numbers refer to the
** For the purpose of this table, you can consider 1 VA = 1 Watt.
122
40K9612
40K9613
32A / 220-
63A/220V-
240V
240V
twelve IEC
twelve IEC
C13
C13
7360VA @
14490VA @
230V
230V
10A
10A
Two C13
Two C13
outlets per
outlets per
breaker
breaker
20A per
20A per
breaker
breaker
32A
63A
Input Line Cords
40K9617
40K9618
32A / 230V
30A / 230V
twelve IEC
twelve IEC
C13
C13
7360VA @
6900VA @
230V
230V
10A
10A
Two C13
Two C13
outlets per
outlets per
breaker
breaker
20A per
20A per
breaker
breaker
32A
30A
section.