4.2.1

Points

You cannot program any wireless points without first completing the steps in Section 1.4 System
Setup on page 5.
Enter a point number from 1 to 32.
Points
1
Record Point Description
For example, if Point 1 is located at the building's front door, say "Front Door" at the tone.
Press [1] to continue programming the selected point.
Press [2] to re-record your current point description.
2
Set Point Type
Press [1] to select the current option.
Press [2] to hear more options.
Press [#] to exit Point Type.
Point Type
Disabled
Perimeter
(Entry or Exit)*
Interior (Follower)*
Perimeter Instant*
24-Hour
Fire Verified
Fire Instant
Silent Panic
Interior Walkthrough*
Perimeter Exit
Cancel*
Momentary Keyswitch
Maintained Keyswitch
#
Exit Points
Return to the Installer Menu.
* An alarm report is not sent to the central station if the system is turned off within the abort window.
Record point programming entries in the Point Programming Entry Tables starting on page 47.
Bosch Security Systems, Inc. | 5/07 | F01U025147-01
Easy Series (ICP-EZM2) | Installer Guide | 4.0 Programming
Description
Point is disabled.
If faulted and the system is on, Entry Delay starts. An alarm occurs if the system is
not turned off when Entry Delay ends.
If the system is on occupied, it ignores these points. If the system is on
unoccupied, a faulted interior point starts an alarm. These points are ignored
during Exit and Entry Delay times.
If faulted when the system is on, a local alarm occurs.
If faulted, an alarm always occurs. To restore a 24-hour point, turn the system off if
it is on, or acknowledge the alarm if the system is off.
If faulted, fire verification occurs. If a second fire event occurs during the two-min.
wait period, a fire alarm occurs. If no second fire event occurs, the system returns
to normal.
If faulted, a fire alarm always occurs.
If faulted, an alarm always occurs. There is no visual or audio indication of the
alarm.
If faulted and the system is on custom protection, Entry Delay starts. If the system
is on occupied or unoccupied, this point functions as an interior point.
If faulted and restored during Exit Delay, Exit Delay stops and the system
immediately turns on.
Turn the system on or off using a momentary keyswitch.
Turn the system on or off using a maintained keyswitch.