Activating Online Operation: Starter Via Profinet Io - Siemens SINAMICS S120 Commissioning Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Commissioning
2.2 STARTER commissioning tool
● Mark the bus node entry and select the displayed menu item "Edit Ethernet node" with
● In the following "Edit Ethernet node" screen, enter the device name for the Ethernet
● The "Update (F5)" button displays the IP address and name in the entry for the bus node.
● If the Ethernet interface is displayed as bus node, mark the entry and click the "Accept"
● The SINAMICS drive is displayed as drive object in the project tree.
● Further configurations can be performed for the drive object.
● Click "Connect to target system" and load the project to the Control Unit's memory card
Note
The IP address and device name are stored on the memory card of the Control Unit in a
non-volatile fashion.
Parameterizing the interface using the expert list
● Assign the "Name of Station" using parameter p8900
● Assign the "IP Address of Station" using parameter p8901 (factory setting 169.254.11.22)
● Assign the "Default Gateway of Station" using parameter p8902 (factory setting 0.0.0.0)
● Assign the "Subnet Mask of Station" using parameter p8903 (factory setting 255.255.0.0)
● Activate the configuration with p8905 = 1
● Activate the configuration and save with p8905 = 2
2.2.4

Activating online operation: STARTER via PROFINET IO

Description
Online operation with PROFINET IO is implemented using TCP/IP.
Preconditions
● STARTER commissioning tool from version 4.1.5 or higher
● Communication Board CBE 20 in the Control Unit
60
the right mouse button.
interface and click the "Assign name" button. For the IP configuration, enter the subnet
mask (255.255.0.0). Then click the "Assign IP configuration" button and close the mask.
If not, close the "Accessible nodes" screen and perform another search for accessible
nodes.
button.
with Target system -> Load -> To target device.
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
Commissioning Manual

Hide quick links:

Advertisement

Table of Contents
loading