F260
Jog Run Frequency
Program  Frequency  Jog
This parameter sets the output frequency of the ASD during a Jog. Jog is the
term used to describe turning the motor on for small increments of time and is
used when precise positioning of motor-driven equipment is required.
The Jog function may be initiated from the EOI, remotely via the ACE G9-
120V-PCB, or using Communications (for additional information on using
Communications for Jogging, see the Communications manual P/N 53840).
The Jog function can be activated from zero Hz or from any frequency below
the Jog Run frequency (Jog can only increase the speed). A Jog command will
not be recognized when the running frequency is above the Jog Run frequency
setting. The Jog command has priority over other Run commands and is not
limited by the Upper Limit setting of parameter F012.
Jog commands received while running for the opposite direction will follow the
programmed stopping method of
ramp to the programmed Jog Frequency and direction.
Jog Setup and Execution
To initiate a Jog Run from the EOI perform the following:
1. Enable the Jog function at F262.
2. Set the Command Mode Selection (F003) to EOI Keypad.
3. Assign the Jog Run setting to a discrete input terminal (see
pg.
236).
Note: Any unused discrete input terminal may be used for the Jog
Run setting.
4. Set up a Jog Run Frequency at F260.
5. Set up a Jog Stop Pattern at F261.
6. Set the Input Terminal Priority (F106) function to Disable to receive
Jog commands from the EOI.
7. Set the Local/Remote key to Local.
8. Activate the Jog Run terminal (from step 3) and provide a Run
command (F or R).
9. Press the Run key and the ASD will output the frequency setting of
for the duration of the activation.
To initiate a Jog Run from the ACE G9-120V-PCB perform the following:
1. Using the setup above, set the Input Terminal Priority (F106) function
(from step 6) to Enable to receive Jog commands from the ACE G9-
120V-PCB using the Jog Run terminal without regard to the Local/
Remote setting.
2. Use the Jog Run terminal of step
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
F261
until reaching zero Hz and will then
3
above to activate the Jog function.
Direct Access Number — F260
Parameter Type — Numerical
Factory Default — 5.00
Changeable During Run — Yes
Minimum —
F240
Maximum — 20.00
Units — Hz
Table 7 on
F260
F260
Setting
129