T8000C PROGRAMMABLE THERMOSTAT
T8000C THERMOSTAT
G
Rc
R
O1
G1
B1
E1
CHANGEOVER
CONTROL
1
JUMPER R TO RC.
Fig. 7. Typical wiring diagram for T8000C on zone 1
MABS II/L control panel.
Setting Fan Operation (Fuel) Switch
The fan operation (fuel) switch is preset at the factory in
the F position. See Fig. 8. This is the correct setting for
most systems. If this system is an electric heat system, set
the switch to the E position. The E setting allows the fan to
turn on immediately with the heating or cooling equipment
in a system where the G terminal is connected.
FAN OPERATION (FUEL) SWITCH
Fig. 8. Fan operation (fuel) switch.

Mounting Thermostat to Wallplate

1. Slide SYSTEM switch to the Off position.
2. Engage the tabs at the top of the thermostat and
wallplate.
3. Swing down the thermostat and press the lower
edge of the thermostat onto the wallplate to latch.
See Fig. 9.
69-1434–1
1
W
B
Y
O
ZONE 1
M12563
E
F
M12580
T8
T7
T6
T5
T4
A
Fig. 9. Mounting thermostat to wallplate.

Installer Setup

°
Setting
F/
The following instructions provide the information neces-
sary to change the heating cycle rate to match the heating
equipment and to choose either Fahrenheit (°F) or Celsius
(°C) display.
NOTE: All four steps must be completed to save
changes to the °F/°C indication and the heat
cycle rate.
4
DASHED LINES INDICATE TABS
ON BACK OF THERMOSTAT
ENGAGE TABS AT TOP OF THERMOSTAT
WITH SLOTS ON WALLPLATE.
H o l d
T U E
B
PRESS LOWER EDGE OF
CASE TO LATCH.
°
C Indication and Heat Cycle Rate
S e l e
c t
M14674